Background Image
Table of Contents Table of Contents
Previous Page  153 / 164 Next Page
Information
Show Menu
Previous Page 153 / 164 Next Page
Page Background

WIRING ACCESSORIES AND SINGLE PHASE DISTRIBUTION

PG00400018U – March 2012

153

Technical data

Control and switching devices dimensions and data

12.6

Contactors type CR, lamp load table

(continued)

Lighting

Lamp load (Watt)

Maximum number of fittings per contactor type

Type

CR 20

CR 25

CR 40

CR 63

Fluorescent lamp – conventional supply

Single fitting – Uncompensated (inductive)

18

22

24

90

140

24

22

24

90

140

36

17

20

65

95

58

14

17

45

70

Single fitting – Compensated (capacative)

18

7

8

48

73

24

7

8

48

73

36

7

8

48

73

58

4

5

31

47

Double fitting – Series compensated

2 x 18

30

40

100

150

2 x 24

24

31

78

118

2 x 36

17

24

65

95

2 x 58

10

14

40

60

Fluorescent lamp – HF electronic

Single fitting – HF Electronic

18

25

31

49

71

24

18

22

35

50

36

14

17

27

39

58

8

10

16

23

Double fitting – HF Electronic

2 x 18

12

15

24

35

2 x 24

9

11

17

25

2 x 36

7

8

13

19

2 x 58

4

5

8

11

Compact fluorescent lamp

Conventional supply

5

38

48

77

121

7

27

34

54

86

9

21

26

42

67

11

17

21

35

55

Electronic supply

5

39

49

78

124

7

39

49

78

124

9

30

38

61

96

11

25

31

50

79

High pressure mercury vapour lamp

Uncompensated

50

14

18

38

55

80

10

13

29

42

125

7

9

20

29

250

4

5

10

15

400

2

3

7

10

Parallel compensated

50

4

5

31

47

80

4

5

27

41

125

3

4

22

33

250

1

2

12

18

400

1

1

9

13

Halogen metal vapour lamp

Uncompensated

35

18

22

43

60

70

10

12

23

32

150

5

7

12

18

250

3

4

7

10

400

3

3

6

9

Parallel compensated

35

5

6

36

50

70

2

3

18

25

150

1

1

11

15

250

-

1

6

9

400

-

1

6

8