Background Image
Table of Contents Table of Contents
Previous Page  151 / 164 Next Page
Information
Show Menu
Previous Page 151 / 164 Next Page
Page Background

WIRING ACCESSORIES AND SINGLE PHASE DISTRIBUTION

PG00400018U – March 2012

151

Technical data

Control and switching devices dimensions and data

12.6

Contactors type CR, technical data

Products

Contactors

Aux. contact

Rating

20 A

25 A

40 A

63 A

6A

General

Standards

IEC 60947-4-1, IEC 61095

IEC 60947-5-1

Nominal operating voltage 1-phase Ue 1-ph.

230 V

230 V

230 V

230 V

230 V

Nominal operating voltage 3-phase Ue 3-ph.

400 V

400 V

400 V

-

-

Overvoltage protection on coil

430 V (*5)

430 V (*5)

430 V

430 V

Mechanical endurance (switching cycles)

3.000.000

3.000.000

3.000.000

3.000.000

3.000.000

Protection class (acc. DIN 40 050, IEC 529)

IP20

IP20

IP20

IP20

IP20

Permissible ambient temperature

-5…+55 ˚C

-5…+55 ˚C

-5…+55 ˚C

-5…+40 ˚C

-5…+55 ˚C

Storage temperature

-30…+80 ˚C

-30…+80 ˚C

-30…+80 ˚C

-30..+80 ˚C

-30…+80 ˚C

Contact rating

Rated insulation voltage Ui

440 V

440 V

500 V

500 V

500 V

Frequency

50/60 Hz

50/60 Hz

50/60 Hz

50/60 Hz‘

50/60 Hz

Rated impulse withstand voltage Uimp

4 kV

4 kV

4 kV

4 kV

4 kV

Rated thermal current Ith

20 A

25 A

40 A

63 A

6 A

AC1 / AC7a Rated operational current Ie

20 A

25 A

40 A

63 A

-

AC1 / AC7a Operational power rating at Ue = 230 Vac Pmax

4 kW

9 kW

16 kW

24 kW

-

AC1 / AC7a Operational power rating at Ue = 400 Vac Pmax

16 kW

26 kW

40 kW

-

-

AC3 / AC7b Operational power rating at Ue = 230 Vac Pmax

1,3 kW (*1)

2,2 kW

5,5 kW

8,5 kW

-

AC3 / AC7b Operational power rating at Ue = 400 Vac Pmax

4 kW

11 kW

15 kW

-

-

DC1 Rated thermal current at Ue = 24 Vdc Ie

20 A

25 A

40 A

63 A

-

DC1 Rated thermal current at Ue = 110 Vdc Ie

1A

2A

4A

4A

-

DC1 Rated thermal current at Ue = 220 Vdc Ie

0,5 A

0,5 A

0,8 A

0,8 A

-

DC1 Rated thermal current at Ue = 24 Vdc

(2-poles in series) Ie

20 A

25 A

40 A

63 A

-

DC1 Rated thermal current at Ue = 110 Vdc

(2-poles in series) Ie

3 A

4 A

10 A

10 A

-

DC1 Rated thermal current at Ue = 220 Vdc

(2-poles in series) Ie

1,5 A

1,5 A

6 A

6 A

-

DC1 Rated thermal current at Ue = 24 Vdc

(3-poles in series)

-

25 A

40 A

63 A

-

DC1 Rated thermal current at Ue =110 Vdc

(3-poles in series)

-

6:00 AM

30 A

35 A

-

DC1 Rated thermal current at Ue = 220 Vdc

(3-poles in series)

-

2,5 A

20 A

30 A

-

Electrical endurance

Maximum operating cycles at AC1 / AC7a application

200.000 x

200.000 x

100.000 x

100.000 x

-

Maximum operating cycles at AC3 / AC7b application

300.000 x

500.000 x

150.000 x

150.000 x

-

Maximum operating cycles at AC5a application

100.000 x

100.000 x

100.000 x

100.000 x

-

Maximum operating cycles at AC5b application

100.000 x (*2)

100.000 x (*2)

100.000 x (*3)

100.000 x (*4)

-

Maximum operating cycles per hour

600 x

600 x

600 x

600 x

600 x

Power dissipation per contact at In

1,7 W

2,2 W

4 W

8 W

-

Maximum back-up fuse

25 A gL

35 A gL

63 A gL

80 A gL

-

Rating

20 A

25 A

40 A

63 A

6 A

Operating coil (for combined ac/dc types only – CR.....)

Coil inrush power (for all voltage ratings)

2,5 W

3 W

5 W

5 W

-

Coil consumption (for all voltage ratings)

2,5 W

3 W

5 W

5 W

-

Closing delay

15-25 ms

15-30 ms

15-20 ms

15-20 ms

-

Opening delay

35-45 ms

50-80 ms

35-45 ms

35-45 ms

-

Operating coil (for ac types only – CR.....A)

Coil inrush power (for all voltage ratings)

13 W / 15 VA

17 W / 27 VA

-

Coil consumption (for all voltage ratings)

2 W / 5 VA

1 W / 2.7 VA

-

-

-

Closing delay

15 ms

15-25 ms

-

-

-

Opening delay

10 ms

35-45 ms

-

-

-