TECHNI CAL DATA

MOTOR RUNN I NG CURRENTS

84

FULL LOAD CURRENTS OF MOTORS (approx)

l

Please note that the kW and HP ratings given below and elsewhere in this publication are to be used only as a guide to the selection of the required starter.

The actual full load current of the motor should be determined to ensure that a starter having a suitably rated overload relay is chosen.

RATING OF MOTOR ALTERNATING CURRENT (A)

Single

phase Three phase

kW HP

240V 220V 380V 415V 440V 500V

0.06 0.08 1.2 0.38 0.22 0.21 0.19 0.16

0.09 0.12 1.5 0.56 0.33 0.30 0.28 0.24

0.12 0.16 1.8 0.76 0.42 0.39 0.37 0.33

0.18 0.25 2.8 1.1 0.58 0.52 0.49 0.46

0.25 0.33 3.2 1.4 0.88 0.71 0.64 0.59

0.37 0.50 3.5 2.1 1.3 1.2 1.1 0.85

0.55 0.75 4.8 2.7 1.5 1.4 1.3 1.2

0.75 1.0 6.2 3.3 2.1 2.0 1.7 1.5

1.1 1.5 8.7 4.9 2.6 2.5 2.3 2.1

1.5 2.0 11.8 6.2 3.6 3.5 3.1 2.6

2.2 3.0 17.5 8.7 5.1 5.0 4.4 3.8

3.0 4.0 20 11.6 6.6 6.5 5.8 5.1

3.7 5.0 24 14.2 8.2 7.5 7.1 6.2

4.0 5.5 29 15.3 8.5 7.7 7.6 6.5

5.5 7.5 36 21 11.5 11 10.3 8.9

7.5 10 45 27 15.5 14 13.5 11.9

11.0 15 70 39 22 21 19.3 16.7

15.0 20 91 53 30 29 27 23

18.5 25 113 64 37 35 32 28

20 27 128 70 40 38 35 31

22 30 135 75 43 40 38 33

25 34 156 85 50 45 42 38

30 40 180 101 60 54 51 44

37 50 124 72 66 62 54

40 54 134 79 77 67 60

45 60 150 85 80 74 65

55 75 181 105 98 90 79

59 80 194 112 105 97 85

75 100 245 140 135 123 106

90 125 292 170 165 146 128

100 134 325 188 179 162 143

110 150 205 200 178 156

129 175 242 230 209 184

132 180 245 236 214 186

147 200 273 259 236 207

160 220 295 278 256 220

184 250 340 325 295 259

200 270 370 350 321 278