TECHNI CAL DATA
MOTOR RUNN I NG CURRENTS
84
FULL LOAD CURRENTS OF MOTORS (approx)
l
Please note that the kW and HP ratings given below and elsewhere in this publication are to be used only as a guide to the selection of the required starter.
The actual full load current of the motor should be determined to ensure that a starter having a suitably rated overload relay is chosen.
RATING OF MOTOR ALTERNATING CURRENT (A)
Single
phase Three phase
kW HP
240V 220V 380V 415V 440V 500V
0.06 0.08 1.2 0.38 0.22 0.21 0.19 0.16
0.09 0.12 1.5 0.56 0.33 0.30 0.28 0.24
0.12 0.16 1.8 0.76 0.42 0.39 0.37 0.33
0.18 0.25 2.8 1.1 0.58 0.52 0.49 0.46
0.25 0.33 3.2 1.4 0.88 0.71 0.64 0.59
0.37 0.50 3.5 2.1 1.3 1.2 1.1 0.85
0.55 0.75 4.8 2.7 1.5 1.4 1.3 1.2
0.75 1.0 6.2 3.3 2.1 2.0 1.7 1.5
1.1 1.5 8.7 4.9 2.6 2.5 2.3 2.1
1.5 2.0 11.8 6.2 3.6 3.5 3.1 2.6
2.2 3.0 17.5 8.7 5.1 5.0 4.4 3.8
3.0 4.0 20 11.6 6.6 6.5 5.8 5.1
3.7 5.0 24 14.2 8.2 7.5 7.1 6.2
4.0 5.5 29 15.3 8.5 7.7 7.6 6.5
5.5 7.5 36 21 11.5 11 10.3 8.9
7.5 10 45 27 15.5 14 13.5 11.9
11.0 15 70 39 22 21 19.3 16.7
15.0 20 91 53 30 29 27 23
18.5 25 113 64 37 35 32 28
20 27 128 70 40 38 35 31
22 30 135 75 43 40 38 33
25 34 156 85 50 45 42 38
30 40 180 101 60 54 51 44
37 50 124 72 66 62 54
40 54 134 79 77 67 60
45 60 150 85 80 74 65
55 75 181 105 98 90 79
59 80 194 112 105 97 85
75 100 245 140 135 123 106
90 125 292 170 165 146 128
100 134 325 188 179 162 143
110 150 205 200 178 156
129 175 242 230 209 184
132 180 245 236 214 186
147 200 273 259 236 207
160 220 295 278 256 220
184 250 340 325 295 259
200 270 370 350 321 278