OVERCURRENT RELEASE AND SWITCH

DISCONNECTOR MODULES FOR TP SWITCHING UNIT

l

Rated Current (

I

n) Overcurrent adjustment (0.4 to 1x

I

n) LIST No

400A

160A .... 400A

7T340/OR3

630A

250A .... 630A

7T363/OR3

• Adjustable overcurrent release

• Adjustable short circuit release

630A

Switch Disconnector

7T363/SD

OVERCURRENT RELEASE MODULES FOR 4P

SWITCHING UNIT

l

Rated Current (

I

n) Overcurrent adjustment (0.4 to 1x

I

n) LIST No

400A

160A .... 400A

7T340/OR4

630A

250A .... 630A

7T363/OR4

• Adjustable overcurrent release

• Adjustable short circuit release

• Protected neutral function

POWERSTAR 250

PANE LBOARDS & I NCOMI NG DEV I CE MODUL ES

35

173T2634

174T2634

7T363/OR4

17INMR630CT

630A PANELBOARD WITH TP SWITCHING UNIT

l

Outgoing TP Height

ways (mm) LIST No

630A

2 1055

173T2632

4 1160

173T2634

6 1265

173T2636

• 630A rated Panelboards

• 900mm wide x 250mm deep (including door)

• Busbar fault rated 50kA for 1 sec

• 250A outgoing TP MCCBs (T2 frame size)

• IP3X (door closed)

• Incoming connections

Incomer: 32mm wide lug connections*

Neutral: 30 x 6mm copper bar 1 x M8 connection

Earth: 25 x 5mm copper bar 1 x M12 connection

• BSEN/IEC 61439-2: 2009

Designation of the incoming device is defined by the selection of an

overcurrent release or Switch Disconnector module.

THE SWITCHING UNIT MUST BE FITTED WITH ONE OF THESE MODULES.

630A PANELBOARD WITH 4P SWITCHING UNIT

l

Outgoing TP Height

ways (mm) LIST No

630A

2 1055

174T2632

4 1160

174T2634

6 1265

174T2636

• 630A rated Panelboards

• 900mm wide x 250mm deep (including door)

• Busbar fault rated 50kA for 1 sec

• 250A outgoing TP MCCBs (T2 frame size)

• IP3X (door closed)

• Incoming connections

Incomer: 32mm wide lug connections*

Neutral: 30 x 6mm copper bar 1 x M8 connection

Earth: 25 x 5mm copper bar 1 x M12 connection

• BSEN/IEC 61439-2: 2009

Designation of the incoming device is defined by the selection of an

overcurrent release.

THE SWITCHING UNIT MUST BE FITTED WITH ONE OF THESE MODULES.

* Dependant on the type of cable lug selected, cables up to 300mm

2

can be connected to these 32mm wide connections

INCOMER INTEGRAL METER PACKS

I

Rating Description LIST No

630A

Integral 3 Ph CT operated Energy meter

17INMK630CT

630A

Integral 3 Ph CT operated Energy meter MID

17INMK630MCT

• Integral meter packs include a digital energy meter, current

transformers, fuses, wiring loom and mounting base plates

Non MID meters include MODBUS (RTU) connections and pulsed output

as a standard feature

MID meters are supplied with a pulsed output as a standard feature