OVERCURRENT RELEASE AND SWITCH

DISCONNECTOR MODULES FOR TP SWITCHING UNIT

l

Rated Current (

I

n) Overcurrent adjustment (0.4 to 1x

I

n) LIST No

250A

100A .... 250A

7T325/OR3

400A

160A .... 400A

7T340/OR3

• Adjustable overcurrent release

• Adjustable short circuit release

400A

Switch Disconnector

7T363/SD

OVERCURRENT RELEASE MODULES FOR 4P

SWITCHING UNIT

l

Rated Current (

I

n) Overcurrent adjustment (0.4 to 1x

I

n) LIST No

250A

100A .... 250A

7T325/OR4

400A

160A .... 400A

7T340/OR4

• Adjustable overcurrent release

• Adjustable short circuit release

• Protected neutral function

34

173T2406

174T2402

7T340/OR3

17INMK400CT

400A PANELBOARD WITH TP SWITCHING UNIT

l

Outgoing TP Height

ways (mm) LIST No

400A

2 1055

173T2402

4 1160

173T2404

6 1265

173T2406

• 400A rated Panelboards

• 900mm wide x 250mm deep (including door)

• Busbar fault rated 35kA for 1 sec

• 250A outgoing TP MCCBs (T2 frame size)

• IP3X (door closed)

• Incoming connections

Incomer: 32mm wide lug connections*

Neutral: 30 x 6mm copper bar 1 x M8 connection

Earth: 25 x 5mm copper bar 1 x M12 connection

• BSEN/IEC 61439-2: 2009

Designation of the incoming device is defined by the selection of an

overcurrent release or Switch Disconnector module.

THE SWITCHING UNIT MUST BE FITTED WITH ONE OF THESE MODULES.

400A PANELBOARD WITH 4P SWITCHING UNIT

l

Outgoing TP Height

ways (mm) LIST No

400A

2 1055

174T2402

4 1160

174T2404

6 1265

174T2406

• 400A rated Panelboards

• 900mm wide x 250mm deep (including door)

• Busbar fault rated 35kA for 1 sec

• 250A outgoing TP MCCBs (T2 frame size)

• IP3X (door closed)

• Incoming connections

Incomer: 32mm wide lug connections*

Neutral: 30 x 6mm copper bar 1 x M8 connection

Earth: 25 x 5mm copper bar 1 x M12 connection

• BSEN/IEC 61439-2: 2009

Designation of the incoming device is defined by the selection of an

overcurrent release.

THE SWITCHING UNIT MUST BE FITTED WITH ONE OF THESE MODULES.

* Dependant on the type of cable lug selected, cables up to 300mm

2

can be connected to these 32mm wide connections

POWERSTAR 250

PANE LBOARDS & I NCOMI NG DEV I CE MODUL ES

INCOMER INTEGRAL METER PACKS

I

Rating Description LIST No

400A

Integral 3 Ph CT operated Energy meter

17INMK400CT

400A

Integral 3 Ph CT operated Energy meter MID

17INMK400MCT

• Integral meter packs include a digital energy meter, current

transformers, fuses, wiring loom and mounting base plates

Non MID meters include MODBUS (RTU) connections and pulsed output

as a standard feature

MID meters are supplied with a pulsed output as a standard feature