Table of Contents Table of Contents
Previous Page  65 / 81 Next Page
Information
Show Menu
Previous Page 65 / 81 Next Page
Page Background

65

Lifeline Range RCDs – Technical

Data

OPERATION

The RCD employs the current balance principle which involves the supply

conductors to the load (phase and neutral) being wound onto a common

transformer core to form the primary windings. Under healthy circuit

conditions, the current in the phase conductor is equal to the current in the

neutral, and the vector sum of the current is zero.

In the event of an earth fault, an amount of current will flow to earth,

creating an out of balance situation in the transformer assembly.

This out of balance is detected by the secondary winding of the transformer

and at a pre-determined level of out of balance will activate the trip

mechanism.

Single phase and neutral or three phase and neutral units (suitable for 3

or 4 wire systems) are available, the latter being suitable for balanced

or unbalanced 3 phase loads.

The RCD trip mechanism will operate at a residual current of between 50–

100% of its rating tripping current (sensitivity).

TRANSIENT EARTH LEAKAGE CURRENTS

AllWylex residual current devices incorporate a high level of immunity to

tripping when subjected to transient earth leakage currents.

Such transients can occur when there is a significant level of capacitance to

earth as can result from cable capacitance (particularly MICC) or RF filter

networks.Wylex RCDs are therefore less susceptible to nuisance tripping

due to transient earth leakage currents.

RESIDUAL TRIPPING CURRENTS

10mA-

Used in special applications where additional protection against contact is

essential due to the nature of the installation.

30mA-

Tripping current designated by the IEEWiring Regulations to provide

additional protection.

100mA-

Suitable for use where protection is provided to guard against firehazard,

etc, rather than to provide additional protection to personnel, and where

the earthing requirements need supplementing by RCD protection.

100mA time delay-

Suitable for use when total RCD protection is required to supplement the

system earthing and where local 30mA RCDs are used to give additional

protection.The time delay RCD will discriminate with the 30mA RCD.

300mA-

For use in large installations where plant and equipment protection are the

main considerations and high levels of earth leakage are experienced.

If using RCDs in series, discrimination can only be achieved by using Type S

devices in series with Types A or AC. See chart below.

IEC PUBLICATION (60479) CURVESWITHWYLEX RCD CHARACTERISTICS SUPERIMPOSED

TIME/CURRENT ZONES OF EFFECT OF AC CURRENT (15–100Hz) ON PERSONS

FAULT CURRENT SENSITIVITY

As the equipment is fed from the mains electrical supply, in the event of

an earth fault the presence of semi-conductors may result in the normal

ac waveform being replaced by a non-sinusoidal fault current. In some

cases the waveform may be rectified or chopped.These waveforms are

said to contain a pulsating dc component which can either partially

desensitise or totally disable a standard Type AC RCD.

International standards IEC 61008 (RCCBs) and IEC 61009 (RCBOs)

divide RCDs into two performance classes:

Type AC

RCDs for which tripping is ensured for residual sinusoidal alternating

currents, whether suddenly applied or slowly arising.

Type A

RCDs for which tripping is ensured for residual sinusoidal alternating

currents and residual pulsating direct currents, whether suddenly

applied or slowly arising.

To ensure the correct level of protection, check for the following

symbols:

TYPEAC

normal ac sensitivity

TYPEA

pulsating dc sensitivity

Wylex RCDs are available as both Type AC and Type A devices.

Technical details for Type B RCDs available on request.

10,000

5,000

2000

1000

500

200

100

50

20

10

0.1 0.2 0.3 0.5 1 2 3 5 10 20 30 50 100 200 300 500 1,000 2,000

10,000

mA

5,000

3,000

Body current in milliamperes (RMS)

100mA

30mA

Typical current

Limits due to body resistance

at 230V

1

2

3

4

a

b

c1 c2 c3

IEC 60479

Time in milliseconds

Zone Physiological effects

1

Usually no reaction effects (no danger).

2

Usually no harmful physiological effects

(usually no effects).

3

Usually no organic damage to be expected.

Likelihood of muscular contraction and

difficulty of breathing, reversible

disturbances of formation and conduction

of impulses in the heart, and transient

cardiac arrest without ventricular fibrillation

increases with current magnitude and time.

4

In addition to the effects of zone 3,

probability of ventricular fibrillation

increased up to 5% (Curve C2), up to 50%

(Curve C3) and above 50% beyond Curve

C3. Increasing with magnitude and time,

pathyphysiological effects such as cardiac

arrest, breathing arrest and heavy burns

may occur.

BSEN61008-1:1995 RCBOs BSEN61009-1:1995

l

Rated Residual Current (

I

n) Tripping

Type of RCD RCD toTrip between times

50%-100%

I

n 1x

I

n 2x

I

n 5x

I

n 500Amps Scope

Standard

AnyValue,eg 10,30,100mA 300ms 150ms 40ms 40ms Maximum-Trip

A &AC

Time Delay

Greater than 30mA,eg 100mA

500ms 200ms 150ms 150ms Maximum-Trip

(S) 130ms 60ms 50ms 40ms Minimum-NonTrip