MCB & RCBO – Technical Data

SHORT CIRCUIT CURRENT AS A MULTIPLE OF RATED CURRENT

OPERATING TIME IN SECONDS

2 HRS

1 HR

1,000

100

10

1.0

0.1

0.01

0.001

1

3

5

10

20

100

1,000

Type

B

Type

C

Type

D

BACK-UP PROTECTION

Back-up protection is required only if the prospective short circuit

current at the point of installation exceeds the breaking capacity of the

MCB.When providing back-up protection consideration must be given

to discrimination between the MCB and fuse.

DISCRIMINATION

It is desirable that the protective device nearest the fault should

operate first.The low energy let through of modern MCBs provides

better discrimination with HRC fuse back-up than is given by earlier

types of MCBs.

CONSUMER UNIT MCBs

Standards BS EN 60898-2 : 2006

Rated voltage (single pole) 240V

Tripping characteristics Type B,C

Short circuit rating 6kA

Reference calibration temperature 30°C

Terminal capacity – outgoing cable 0.75 to 25mm

2

CAT REF C CURVE RATING

NHXB06 NHXC06 6A

NHXB10 NHXC10 10A

NHXB16 NHXC16 16A

NHXB20 NHXC20 20A

NHXB32 NHXC32 32A

NHXB40 NHXC40 40A

NHXB50 NHXC50 50A

4x10

2

Prospective short circuit current Ip/A

Let-through I

2

t (amp

2

/sec)

10

3

6 8 10

3

2 3 4 6 10

4

8

I

n

=

2

3

4

6

8

10

4

2

3

4

6

8

10

5

40 A

32 A

25 A

20 A

16 A

10 A

6 A

50 A

40 A

35 A

32 A

63 A

80 A

100 A

125 A

BS88 FUSE 160A

2

1

1

HW = 0.01 sec

2

min melting pt (pre-arching)

eg I

n

=125A BS 88

max let-through I

2

t of MCB

eg 6A

4x10

2

Prospective short circuit current Ip/A

Let-through I

2

t (amp

2

/sec)

10

3

6 8 10

3

2 3 4 6 10

4

8

I

n

=

2

3

4

6

8

10

4

2

3

4

6

8

10

5

40 A

32 A

25 A

20 A

16 A

10 A

6 A

50 A

40 A

35 A

32 A

63 A

80 A

100 A

125 A

BS88 FUSE 160A

2

1

1

HW = 0.01 sec

2

min melt g pt (p e-arching)

eg I

n

=125A BS 88

max let-through I

2

t of MCB

eg 6A

1 1.5 2 3 4 5

3 5

6 8 10 15 20 30

0.01

0.02

0.04

0.06

0.1

0.2

0.4

0.6

1

2

4

6

10

20

40

1

2

4

6

10

20

40

60

120

Tripping time

Minutes

Seconds

1.13 1.45

7

Multiple of rated current

ac

NHX, NSB AND PSB DISTRIBUTION BOARD

MCBs

Standards BSEN 60898 -2: 2006

RatedVoltage 230/400Volts

Tripping characteristics Type B, C and D

Short circuit rating 6kA and 10kA

Reference calibration

temperature 30˚C

Terminal capacity -

outgoing cable 0.75 to 25mm

2

NHXSBS, NSBS & PSBS RCBO

(COMBINED MCB/RCD)

Standards BSEN 61009 -2: 1995

BSEN 61009 -1: 2004

RatedVoltage 230Volts -1 2004

SP or SP with switched neutral

Tripping characteristics NSBS=B,C PSBS=C

Short circuit rating 6kA and 10kA

Reference calibration

temperature 30˚C

Rated residual operating

current 30mA

Single module Type A

Two module Type AC

Terminal capacity - 0.5 to 16mm

2

outgoing cable

Unique live side busbar combi-terminal allows

connection of cable up to 25mm

2

Maximum neutral cable size 25mm

2