Background Image
Table of Contents Table of Contents
Previous Page  229 / 267 Next Page
Information
Show Menu
Previous Page 229 / 267 Next Page
Page Background

3VT5 Molded Case Circuit Breakers up to 1600 A

Accessories and Components

Shunt trip units

6/27

Siemens LV 36 · 2008

6

Technical specifications

Technical specifications

Circuit breaker switched off by shunt release

Circuit breaker states and lever positions of circuit breakers

Order No.

3VT9 500-1S.00

Rated operating voltage U

e

V

AC 24, 48, 110, 230, 400, 500

DC 24, 48, 110, 220

Rated frequency f

n

Hz

50/60

Input power at 1.1 U

e

AC

DC

< 2.5 VA

< 2 W

Characteristic

U

0,7U

e

the circuit breaker must

trip

Time to switch-off

ms

20

Loading time

Connection cross-section S mm

2

0.5 ... 1

Terminal protection

(connected releases)

IP20

Location in accessory com-

partment No.

5

Circuit breaker state

lever positions of circuit breakers

Switched on

Switched off by releases, or by TEST

button or by the trip push button on

the motor drive

Switched off manually or electrically

by drive

20

30

30

30

0

1

0

1

0

1

0

1

0

1

t

[ms]

30

NSO0_00470

2

4

6

1

3

5

1.44

1.14

1.43

1.13

2.14

2.44

2.13

2.43

1.32

1.22

1.31

1.21

2.22

2.32

2.21

2.31

3.44

3.14

3.43

3.13

4.14

4.44

4.13

4.43

3.32

3.22

3.31

3.21

4.22

4.32

4.21

4.31

Main contacts

Auxiliary switch

Auxiliary switch

Relative switch

Relative switch

accessory

compartment

3 + 4

accessory

compartment

1 + 2

B1

U

B2

N-

3VT9 500-1S.00

L+

NSO0_00467