3VT5 Molded Case Circuit Breakers up to 1600 A
Accessories and Components
Signalling units
6/25
Siemens LV 36 · 2008
6
■
Technical specifications
The 3VT9 5006AE00 signalling unit is a modular accessory for
the 3VT4 and 3VT5 circuit breakers and collaborates with the
electronic releases 3VT9 5..-6AC00, 3VT9 5..-6AP00 and
3VT9 5..-6AD00.
• It is intended for applications in automated-control systems
• The unit signals reaching a certain current value in a circuit
and the tripping of the circuit breaker by releases (dependent,
independent, undercurrent)
- user has a options to set up (by steps, using a rotary switch)
an amount of current he wishes to indicate if it has been
reached
- the options are 70; 80; 90; 100; 120; 140; 160 or 180%
I
r
(refer to the Table below for more details).
• Local indication regarding the state of the circuit breaker and
the protected circuitry is carried out by LED indicators on the
front panel of the unit
• The information on the state of the circuit breaker is transferred
from the release to the signalling unit by means of optical cou-
pling
• Remote indication on the state of the circuit breaker and the
protected circuitry is ensured by a relay, the make and break
contacts of which are pulled into the terminal strip on the unit
- relays to indicate tripping of dependent or undercurrent and
independent releases have storage
- after the storage relay is activated by tripping of a release,
it is necessary to reset the relay using the front panel RESET
switch or by an external push button remotely.
• The supply voltages are presented in the table
• The main power supply and the reset circuit are not concur-
rently conformable with conditions for safe separation of the
circuits
• The external RESET button must be connected using a
screened cable or a twisted wire with maximum resistance of
the loop 100 Ohm.
The signalling unit will not work without power supply!
Specifications
Main circuit status indication
1, 2
supply
6, 7
external RESET button
9, 10, 11 relay contacts indicating preset
I
r
12, 13, 14 relay contacts indicating reaching 110%
I
r
15, 16, 17 relay contacts indicating tripping by dependent or
undercurrent releases
18, 19, 20 relay contacts indicating tripping by independent
release (instantaneous or delayed ones)
Order No.
3VT9 500-6AE00
Rated operating voltage U
e
AC/DC 12 ... 230 V
Protection (tube fuse)
T1.5 A
Rated frequency f
n
50/60 Hz
Current draw (rms) max. at U
e
AC-15
DC-13
AC/DC 12 V
AC/DC 24 V
AC/DC 48 V
AC/DC 110 V
AC 230 V/DC 220 V
370 mA
170 mA
100 mA
60 mA
50 mA
Rated operating current
(of relay contacts)
I
e
/U
e
AC-1
DC-1
8 A/AC 230 V
0.25 A DC 250 V, 8 A/DC 30 V
Connection cross-section S
0.5 ... 1 mm
2
Signalling
(relay contacts)
LED
Reaching
<
70%
I
r
--
+
110%
I
r
+
+
70; 80; 90; 100; 120; 140; 160; 180 --
+
Settings
+
+
Release tripping
By dependent/undercurrent
+
+/+
Independent
+
+
NSO0_00465
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
AC/DC
12 - 230 V
I
> … %
I
r
I
> 110 %
I
r
I
>
I
r
I
>
I
sd
N
3 < m M
3~
Power
RESET