Background Image
Table of Contents Table of Contents
Previous Page  228 / 267 Next Page
Information
Show Menu
Previous Page 228 / 267 Next Page
Page Background

3VT5 Molded Case Circuit Breakers up to 1600 A

Accessories and Components

Auxiliary switches

6/26

Siemens LV 36 · 2008

6

Technical specifications

Technical specifications

1)

PS-BL-....-Au is not suitable to control electromagnetic loads

Functions and names of switches according to their location in

cavities

Wiring diagramm

Order No.

3VT9 500-2AF10 3VT9 500-2AF20

1)

Rated operating voltage U

e

V AC 60 ...500 V

DC 60 ...240 V

AC 5 ...60 V

DC 5 ...60 V

Rated islation voltage U

i

V 500

Rated frequency f

n

Hz 50/60

Rated operating current

I

e

/U

e

AC-15

DC-13

6 A/60 V ... 240 V, 3 A/400 V,

1.5 A/500 V

1 A/60 V, 0.7 A/110 V, 0.3 A/240 V

Thermal current

I

th

A 6 A

0.5 A

Arrangement of contacts

22

Connection cross-section S mm

2

0.5 ... 1

Terminal protection

(connected switch)

IP20

Arrangement of contacts Number of contacts Contact types

22

2 + 2

break + make

Switch location Switch name Switch function

accessory

compartment 1, 2

Auxiliary switch to indicate the position of the main

contacts

accessory

compartment 3, 4

Relative switch to indicate tripping of circuit breaker

by release, TEST push button or by

motor

NSO0_00466

2.13

2.14

2.21

2.22

2.31

2.32

2.43

2.44

3.13

3.14

3.21

3.22

3.31

3.32

3.43

3.44

4.13

4.14

4.21

4.22

4.31

4.32

4.43

4.44

1.13

1.14

1.21

1.22

1.31

1.32

1.43

1.44

3VT9 500-2AF10

3VT9 500-2AF10

3VT9 500-2AF10

3VT9 500-2AF10

Switches

acc. comp. no. 2 acc. comp. no. 3 acc. comp. no. 4

acc.comp. no. 1

auxiliary

relative

relative

auxiliary