Table of Contents Table of Contents
Previous Page  320 / 336 Next Page
Information
Show Menu
Previous Page 320 / 336 Next Page
Page Background

16/22

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

16

Technical reference

Earthing standards

Installation of a well designed earthing system is a

fundamental requirement for all structures and electrical

systems (at all voltages).

Effective earthing safeguards people from risk of electric

shock, in that

‘hazardous-live-parts shall not be accessible

and accessible conductive parts shall not be hazardous live’

,

and ensures a low impedance route to the general mass of

earth for currents in the electrical system, under both normal

and fault conditions.

A number of national and international standards have been

published which define earthing system design parameters for

structures, electrical equipment and systems, including:

BS EN 50522:

Earthing of power installations

exceeding 1kVac

BS 7430:

Code of practice for protective earthing of

electrical installations

BS 7354:

Code of practice for design of high voltage open

terminal stations

IEEE Std 80:

IEEE Guide for safety in AC

substation grounding

ENA TS 41-24

Guidelines for the design, installation, testing

and maintenance of main earthing systems in substations

The design, specification, inspection and periodic testing

of earthing systems should follow the guidance and

recommendations provided by these standards.

BS 7430: Protective earthing of electrical installations

British Standard BS 7430 provides guidance on earthing of

general land-based electrical installations in and around

buildings in the UK, including:

–– Low voltage installation earthing and equipotential bonding

for general, industrial and commercial buildings, locations

with increased risk, rail systems etc

–– The interface between low voltage and high voltage substations

–– Earthing of generators and Uninterruptible Power Supplies

(UPSs) supplying low voltage installations

BS 7430 defines the elements for creating an appropriate

earthing arrangement for a low voltage installation, including a

main earthing terminal, protective conductors, earthing

conductors and circuit protective conductors, and the use of

earth electrodes to dissipate currents to the general mass

of earth. Extending the earthing arrangement through the use

of equipotential bonding measures to cover exposed and

conductive metal parts is further recommended to protect

against step and touch voltages, and to remove risk of

dangerous sparking. Five classes of low voltage electrical

installation are defined within the standard - TN-S, TN-C,

TN-C-S, TT and IT.

Performance requirements for earthing these low voltage

installations are defined in the IET Wiring Regulations,

BS 7671:2008(+A1:2011).

The earthing arrangement should be sufficiently robust to

ensure it lasts the lifetime of the installation, and be protected

from mechanical damage and corrosion so that it remains

capable of carrying the maximum expected current, it is

specified for under both normal and fault conditions.

BS 7430 therefore defines selection parameters for the earth-

ing arrangement, e.g. the size and material for conductors,

earth electrodes etc, and makes clear the need for careful

consideration of site conditions (soil composition and resistivity).

Taking actual measurements at the site is important to gauge

the expected effectiveness of the earthing arrangement,

and guidance is provided for measuring resistance

calculations for earth plates, earth rods, ring conductor and

foundation earth electrodes.

Where necessary in high resistivity areas or on rocky ground,

treatment of the soil through use of an earth electrode

backfill is recommended to improve earth contact resistance.

Substation earthing

BS 7354, IEEE std. 80 and ENA TS 41-24 reference the

requirements for earthing of substations.

The design and specification of an appropriate earthing

arrangement for substations is essential to provide a low

impedance path for earth fault, and lightning currents, and to

protect personnel on site from potentially fatal step and

touch voltages. These standards provide guidance on (but

not limited to):

–– Maximum permitted step and touch voltages

–– Methods for calculating earthing system design

–– High voltage earth electrode selection, including type,

material and size

–– Switching and busbar arrangement

–– Equipotential bonding

–– Insulation co-ordination

Primary to these standards is limiting earth potential rise (EPR)

under earth fault conditions so that step and touch potential

limits are not exceeded, and earth resistance remains as

low as possible. Essentially, use of an earthing grid consisting

of horizontal cross-bonded earthing conductors is

recommended, augmented by earth rods where the site

includes low resistivity layers beneath the surface. These earth

rods mitigate seasonal variations in earth grid resistance at

the grid’s burial depth.