Background Image
Table of Contents Table of Contents
Previous Page  235 / 300 Next Page
Information
Show Menu
Previous Page 235 / 300 Next Page
Page Background

TSC-0912 - 09.10.12

Furse, Wilford Road, Nottingham, NG2 1EB • Tel: +44 (0)115 964 3700 • Email:

enquiry@furse.com

• Web:

www.furse.com

ESP TN/JP, TN/RJ11 & ISDN/RJ45 Series

Technical specification

106 mm

54 mm

49 mm

Depth: 24 mm

Fixing centres 49 x 54 mm, M3 clearance

E

60 mm

ESP TN/RJ11-2/6, 4/6, 6/6

cable length: 1 m

ESP TN/JP

cable length: 1 m

ESP ISDN/RJ45-4/8, 8/8

cable length: 0.5 m

1

Maximum working voltage (DC or AC peak) measured at

< 10 µA leakage for ESP TN/JP and ESP TN/RJ11 products and

5 µA for ESP ISDN/RJ45 products.

2

Maximum working voltage is 5 V for pairs 3/6 & 4/5, and

58 V for pairs 1/2 & 7/8.

3

The maximum transient voltage let-through of the protector

throughout the test (±10%), line to line & line to earth, both

polarities. Response time < 10 ns.

4

Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,

K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,

ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68).

5

The first let-through voltage value is for pairs 3/4 & 5/6, and

the second value is for pairs 1/2 & 7/8.

6

The installation and connectors external to the protector may

limit the capability of the protector.

Electrical specification

ESP TN/JP

ESP TN/

ESP TN/

ESP TN/

ESP ISDN/

ESP ISDN/

RJ11-2/6

RJ11-4/6

RJ11-6/6

RJ45-4/8

RJ45-8/8

Nominal voltage

296 V

296 V

296 V

296 V

5 V

5 V/58 V

2

Maximum working voltage

U

c

1

296 V

296 V

296 V

296 V

58 V

58 V

Current rating

(signal)

300 mA

In-line resistance

(per line ±10%)

4.4

Bandwidth

(-3 dB 50

system)

20 MHz

20 MHz

20 MHz

20 MHz

19 MHz

19 MHz

Transient specification

ESP TN/JP

ESP TN/

ESP TN/

ESP TN/

ESP ISDN/

ESP ISDN/

RJ11-2/6

RJ11-4/6

RJ11-6/6

RJ45-4/8

RJ45-8/8

Let-through voltage

(all conductors)

3

U

p

C2 test 4 kV 1.2/50 µs,

- line to line

2 kA 8/20 µs to

- line to earth

BS EN/EN/IEC 61643-21

395 V

395 V

395 V

395 V

395 V

395 V

395 V

395 V

28 V

88 V

28 V/88 V

5

88 V

C1 test 1 kV, 1.2/50 µs,

- line to line

0.5 kA 8/20 µs to

- line to earth

BS EN/EN/IEC 61643-21

390 V

390 V

390 V

390 V

390 V

390 V

390 V

390 V

23 V

63 V

23 V/63 V

5

63 V

B2 test 4 kV 10/700 µs to - line to line

BS EN/EN/IEC 61643-21

- line to earth

298 V

298 V

298 V

298 V

298 V

298 V

298 V

298 V

26 V

65 V

26 V/65 V

5

65 V

5 kV, 10/700 µs

4

- line to line

- line to earth

300 V

300 V

300 V

300 V

300 V

300 V

300 V

300 V

27 V

80 V

27 V/80 V

5

80 V

Maximum surge current

6

D1 test 10/350 µs to BS EN/EN/IEC 61643-21

1 kA

ITU-T K.45:2003, IEEE C62.41.2:2002

10 kA

Mechanical specification

ESP TN/JP

ESP TN/

ESP TN/

ESP TN/

ESP ISDN/

ESP ISDN/

RJ11-2/6

RJ11-4/6

RJ11-6/6

RJ45-4/8

RJ45-8/8

Temperature range

-40 to +80 ºC

Connection type

Standard BT jack

plug and socket

(to BS 6312)

RJ11 plug

and socket

RJ11 plug

and socket

RJ11 plug

and socket

RJ45 plug

and socket

RJ45 plug

and socket

Earth connection

M4/DIN rail

Case material

ABS UL94 V-0

Weight -

unit

0.15 kg

-

packaged

0.2 kg

Dimensions