Technical

information

ULTI

Frequently asked questions

Questions

Answers

1. Is two way / intermediate control acheivable using ULTI?

Yes. By using a FreeLocate switch

2. What is the purpose of 047uF load capacitor UAX004?

This capacitor should be used for specific lamp types where

minimum load requirements are not met

3. What size of mounting box should be used with

A 35mm or deeper back box should be used. ULTI switches and

dimmers?

Trouble shooting guide

Symptom

Possible cause

Solution

Switch / Dimmer is not responding

to the Remote Control Unit

1. Not previously programmed or improper

Repeat the Programming Procedures explained

programming. in the Manual.

2. Switch/Dimmer is set to Programme mode.

The LED indicator is turned on red now, indicating

the unit is in Programming mode. Programme

button to exit Programming mode.

3. Voltage is too low.

Make sure the operating voltage range is within the

requirement.

4. Power rating is too low

Replace a load that meets the minimum loading

requirement.

5. RF wireless control is disabled. (Programme

flashes continuously in the pattern of 2)

Press the Programme Button of the LED Switch/

Dimmer 6 times within 1 minute. Programme LED

should stop flashing.

Unable to programme.

1. Red Programme LED flashes after the

This indicates the memory is full. Perform

Programme Button is pressed. Memory Clearing

Procedures to release space.

2. The Switch does not receive programming

Check the position of the function selector at the

commands. back of the FreeLocate Switch. Make

sure it is in the Programme position.

3. RF wireless control is disabled. (Programme

flashes continuously in the pattern of 2)

Press the Programme Button of Switch 6 times

within 1 minute. Programme LED should stop

flashing.

Main light or LED backlight does

not turn on.

1. Wires are not properly secured or connected

Make sure the wires are secured, screws are in the

terminals. fastened and the Live or Load wires have

been connected to the correct terminals.

2. MCB is OFF or has been tripped.

Switch on the MCB. If a breaker continually trips,

contact a registered electrician to find out the cause

of the problem

3. Temporary disorder.

Switch off the MCB and then on again to reset the

switch.

Main load is turned off

automatically.

1. Power rating is too low.

Replace the load that meets the minimum loading

requirement.

2. Wires are not properly secured in the

Make sure the wires are secured and screws are

terminals. Fastened properly.

3. Controlled by other remote control unit within

Determine which remote control unit(s) is (are) the

area. controlling the particular main light. (Refer to

Memory Clearing Procedures).

Programme LED flashes

continuously in a pattern of 2 for 1

minute then stops.

Pattern continues when Control

Button is pressed again.

1. Low Volt Halogen (12V) is blown

Replace the lamp load if it is blown, then perform a

unit reset.

2. Magnetic transformer is faulty.

Check the status of magnetic transformer.