D-71
Additional information
Enclosure characteristics
Selection of enclosures
according to the premises
Type of premises
Enclosure
Cubicle
with fixed frame with door + IP30
cover
with door + gasket
+ IP30 cover
with door + IP55
cover
Min. IP/IK
required
IP30/IK07
IP30/IK08
IP31/IK08
IP43/IK08
IP55/IK10
IP IK
Technical premises
Battery rooms
23
02/07
bb
Lifts (machine rooms and pulley
rooms)
20
07
v
/08
b
bb
bb
Electrical rooms
20
07
bb
Control rooms
20
02
bb
Workshops
21
v
/23
b
07
v
/08
b
bb
bb
Laboratories
21
v
/23
b
02
v
/07
b
bb
bb
Air conditioning washers
24
07
bb
Garages (used exclusively for
parking vehicles) of an area not
exceeding 100 m
2
21
07
bb
Machine rooms
31
07/08
bb
Water pressurisers
23
07/08
bb
Boiler houses and adjoining premises (power in excess of 70 kW)
Boiler rooms
coal fuel
51
v
/61
b
07
v
/08
b
bb
other fuel
21
07/08
bb
electrical
21
07/08
bb
Fuel
storage areas
coal
50
v
/60
b
08
bb
oil
20
07
v
/08
b
bb
bb
liquefied gas
20
07
v
/08
b
bb
bb
Cinder tips
50
08
bb
Pump rooms
21
v
/23
b
07
v
/08
b
bb
bb
Pressure reduction rooms (gas)
20
07
v
/08
b
bb
bb
Steam or hot water facilities
21
v
/23
b
07
v
/08
b
bb
bb
Expansion vessel room
21
02
bb
Garages and car parks of an area exceeding 100 m
2
Parking lots
21
07
v
/10
b
bb
bb
Carwash areas (inside premises)
25
07
bb
Petrol stations inside
21
07
bb
outside
Lubrication areas
23
08
bb
Battery recharging areas
23
07
bb
Workshops
21
08
bb
Public building (other than for the general public)
Offices
20
02
bb
Libraries
20
02
bb
Archives
20
02
bb
Computer rooms
20
02
bb
Design offices
20
02
bb
Rooms containing reprographic
machines
20
02
bb
Sorting rooms
20
07
bb
Refectories in restaurants or
canteens
21
07
bb
Large kitchens
Sports rooms
20
07
v
/08
b
bb
bb
Barracks
20
07
bb
Meeting rooms
20
02
bb
Waiting rooms, lounges, halls
20
02
bb
Medical consulting rooms, not fitted
with specific equipment
20
02
bb
Demonstration and exhibition rooms 20
02/07
bb
No applicable