C-27

Regulating

The thermostat can control the temperature inside electrical switchboards in

conjunction with heating resistors and fans.

This thermostat can control the activation of a fan and a heater and regulate their

temperature independently.

Mecanical thermostats

Electronical thermostats

PB501172_R.eps

PB501162_30.eps

PB501173_R.eps

PB501174_R.eps

PB502513.eps

Thermostat

with OF contact

Double thermostat

Electronical

thermostat

Electronic

hygrotherm

Electronic hygrostat

Cat. no.

NSYCCOTHI

NSYCCOTHD

NSYCCOTH230VID NSYCCOHYT230VID NSYCCOHY230VID

Colour of the button Black

bb

Red: with normally closed

contact (NC) for controlling

the resistance heaters.

bb

Blue: with normally open

contact (NO) for controlling

the fans, signalling systems

or alarms.

-

-

-

Contact

Inverse, forced rupture 1 with normally closed

contact (NC),

1 with normally open contact

(NO),

forced rupture

Free with zero potential

Internal sensor

element

Bimetal

Internal temperature

sensor

-

Internal humidity sensor

Switching capacity 250 V AC ; 10 A (resistive

load)

250 V AC ; 10 A

120 V AC ; 15 A

250 V AC/120 V AC : 2 A

(inductive load cos Ø= 0,6)

30 W DC

-

-

-

Max interrupting

capacity with direct

current

250 V AC 4 A

(charge inductive Ø = 0,6)

30 W DC

-

-

-

-

Connection

Four 2.5 mm² terminals Six 2.5 mm² terminals

2 x 2.5 mm² (input voltage)

+ 2 relays (2 x 2.5 mm²

+ 2 x 2.5 mm²)

2 x 2.5 mm² (input voltage)

+ 2 relays (2 x 2.5 mm²

+ 2 x 2.5 mm²)

2 x 2.5 mm² (input voltage)

+ 1 relay (2 x 2.5 mm²)

Dimensions (mm)

67 x 50 x 44

60 x 33 x 43

-

-

-

Weight (g)

100

40

-

-

-

Hysteresis

7° K

7° K

Programmed 2 °K

3 %

3 %

Temperature setting

range

+5...+60 °C

0...+60 °C

-40 °C…+80 °C

-40 °C…+80 °C

-40 °C…+80 °C, humidity

setting range:20 %…80 %

Characteristics

bb

Ingress protection rating: IP20.

bb

Contact resistance: < 10 m

W.

bb

Service life: > 100 000 cycles.

bb

Fixing:by clip on a 35-mm DIN rail

bb

Case : plastic UL 94 V-0, light grey.

bb

Operating temperature : -20...+80 °C (-4...+176 °F).

bb

Display : °C/°F.

bb

Max. command intensity: (NC) 5 A (NO) 10 A.

bb

Ingress protection rating: IP20.

bb

Certification : UL/UR.

bb

Fixing: 4 different methods: on DIN rail, Spacial SF profile, on VDI cross-rail or on

mounting plate

bb

Boîtier : plastique UL 94 V-0, gris clair.

bb

Operating temperature : -40 °C…+80 °C.

bb

Display : °C/°F.

bb

Max. command intensity: 8 (5) A 230 V AC / 5 A 30 V DC.

PTC external temperature sensor (double insulation)

PB501175_R.eps

Cat. no.

NSYCCASTE

Characteristics

bb

Sensor operation or reading range: -30 °C…+80 °C.

bb

IP67.

bb

Thermostat installation tips: the thermostat should be installed at the top of the enclosure (the hottest place). See the various operating

modes of each thermostat to choose the one that best meets your needs.

bb

Hygrostat installation tips: the hygrostat should be installed at the bottom of the enclosure. 60 % RH is the optimum value in the enclosure.

Thermal management of switchboards