![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0186.jpg)
B-50
Distribution
Secondary distribution
Linergy TB
terminal block support
Introduction
In Prisma P cubicles, terminal blocks are commonly installed in a lateral
compartment, generally 300 or 400 mm wide.
They may also be installed at the top or bottom of the cubicle.
Dd383711.eps
Installation at top or bottom
of a cubicle
Installation in a lateral
compartment
Installation on a device
mounting plate
Dd381512.eps
Dd381513.eps
Dd381514.eps
Modular rail, depth adjustable (W = 432 mm)
03402
-
-
2 modular rails W = 1600 mm
04226
04226
-
2 universal angle brackets
03581
03581
-
Set of two lateral cross-members W = 400 mm
03584
-
-
Cable-tie supports
-
see page A-79
-
Characteristics
Terminal blocks are grouped on
modular rails that can be depth
adjusted behind a plain front plate.
The terminal block is generally
installed in the cable
compartment, W = 300 or
400 mm.
The terminal blocks clip onto a
modular rail. The rail is secured to
cable-tie supports using universal
angle brackets for precise
positioning of the terminal blocks.
Terminal blocks can be directly
installed on the mounting plates
for horizontally mounted Compact
NSX100/630 and vertically
mounted Compact NS630b/1600
for connection of auxiliary wires.
Width of standard terminal blocks
Max. cable CSA (mm²)
4
6
10
16
Width of terminal block (mm)
6
8
10
12
Height required in switchboard
Max. cable CSA (mm²)
4
6
10
16
No. of vertical modules
3
3
5
6
Plain front plate
03803
03803
03805
03806