![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0178.jpg)
B-42
Linergy FH
Comb busbar for 18 mm pitch for Acti 9
Distribution
Device feeders
PB502380-30.eps
IEC 60947-7-1, IEC 61439-2
Description
bb
Comb busbars make it easier to install Acti 9 circuit breakers.
bb
The phases are identified by symbols on each side of the comb busbar for
installation in all positions.
Acti 9
18 mm poles, not cuttable
Number of poles
1P
2P
3P
4P
3 (N + P)
PB110231-15.eps
Rated operational current to 40 °C (Ie)
100 A
Rated conditional short-circuit
current of an assembly
(Isc) Compatible with the breaking capacity of Acti 9 circuit breakers
Rated insulation voltage
(Ui) 500 V AC
Rated voltage
(Ue) 415 V AC
Degree of pollution
3
Fire resistance to IEC 695-2-1
Self-extinguishing 960 °C, 30 s
Colour
RAL 7016 (anthracite grey)
Use
Power supply by connector recommended
Type
L1
L1L2
L1L2L3
NL1L2L3
NL1NL2NL3
Set of
1
1
1
1
1
Catalogue numbers
12 modules of 18 mm
A9XPM112
A9XPM212
A9XPM312
A9XPM412
A9XPM512
(1)
(1)
This comb busbar is only compatible in top feeding for simple lug devices and bottom feeding on double lug devices.
Installation
PB110290-25.eps
PB110793-25.eps
Accessories
PB110257-10.eps
PB110258-7.eps
PB110259-7.eps
Tooth caps
Connectors
Monoconnect
Double terminals
To insulate teeth that have been left free
Comb busbar power supply
Use
Horizontal incomer on each side
For 35 mm
2
cable
Tightening torque 4 N.m
Set of
20
4
4
Catalogue
numbers
A9XPT920
A9XPCM04
A9XPCD04
Installation
PB108162-35.eps
PB108164-35.eps