Table of Contents Table of Contents
Previous Page  176 / 338 Next Page
Information
Show Menu
Previous Page 176 / 338 Next Page
Page Background

B-42

Linergy FH

Comb busbar for 18 mm pitch for Acti 9

Distribution

Device feeders

PB502380-30.eps

IEC 60947-7-1, IEC 61439-2

Description

bb

Comb busbars make it easier to install Acti 9 circuit breakers.

bb

The phases are identified by symbols on each side of the comb busbar for

installation in all positions.

Acti 9

18 mm poles, not cuttable

Number of poles

1P

2P

3P

4P

3 (N + P)

PB110231-15.eps

Rated operational current to 40 °C (Ie)

100 A

Rated conditional short-circuit

current of an assembly

(Isc) Compatible with the breaking capacity of Acti 9 circuit breakers

Rated insulation voltage

(Ui) 500 V AC

Rated voltage

(Ue) 415 V AC

Degree of pollution

3

Fire resistance to IEC 695-2-1

Self-extinguishing 960 °C, 30 s

Colour

RAL 7016 (anthracite grey)

Use

Power supply by connector recommended

Type

L1

L1L2

L1L2L3

NL1L2L3

NL1NL2NL3

Set of

1

1

1

1

1

Catalogue numbers

12 modules of 18 mm

A9XPM112

A9XPM212

A9XPM312

A9XPM412

A9XPM512

(1)

(1)

This comb busbar is only compatible in top feeding for simple lug devices and bottom feeding on double lug devices.

Installation

PB110290-25.eps

PB110793-25.eps

Accessories

PB110257-10.eps

PB110258-7.eps

PB110259-7.eps

Tooth caps

Connectors

Monoconnect

Double terminals

To insulate teeth that have been left free

Comb busbar power supply

Use

Horizontal incomer on each side

For 35 mm

2

cable

Tightening torque 4 N.m

Set of

20

4

4

Catalogue

numbers

A9XPT920

A9XPCM04

A9XPCD04

Installation

PB108162-35.eps

PB108164-35.eps