Standard individual

check sheet

in accordance with the IEC 61439-1

and 2 standard from the assembly

manufacturer (panelbuilder)

Job No.: .................................................................................................

Switchboard No.: ...................................................................................

Drawing No./Rev. No.: ............................................................................

Chapter

Verified

Degrees of protection provided by enclosures

11.2

Insulation clearances and creepage distances

11.3

Protection against electric shocks and integrity

of protection circuits

11.4

Integration of incorporated components

11.5

Internal electric circuits and connections

11.6

Terminals for external conductors

11.7

Mechanical operation

11.8

Dielectric properties

11.9

Wiring, operating performance and function

11.10

Date of verification:

............ / ............ /.............

Verifications performed by:

..........................................................................…………………………

IEC 61439-1 paragraph 11.6

Internal electric circuits

and connections

Schneider Electric recommends marking

the nut with a tinted acrylic lacquer, indelible

and temperature-resistant.

This allows:

>

not only self-checking to check effective

tightening to torque;

>

but also identification of any loosening.

IEC 61439-1 paragraphe 11.9

Dielectric properties

The main circuits, and the auxiliary and

control circuits connected to the main circuit,

shall be subjected to the test voltage in

accordance.

IEC 61439-1 paragraph 11.10

Wiring, operating performance

and function

Verification of wiring and marking conformity

with the drawings, parts list and diagram.

IEC 61439-1 paragraph 11.4

Protection against electric shocks

and integrity of protection circuits

The following should be checked visually:

>

presence of protective shields against

direct and indirect contacts on live parts;

>

presence of the PE conductor.

The continuity of protection circuits is

ensured by compliance with the assembly

instructions delivered with each product.

IEC 61439-1 paragraph 11.5

Integration of incorporated

components

The assembly manufacturer must comply

with the instructions of the original equipment

manufacturer for installation