Once the dissipated power of the devices has been determined and the enclosure

with its IP selected, transfer the results (sum of the dissipated power and width of the

device zone) to the chart corresponding to the enclosure IP.

Draw a line parallel to the others on the chart and read the corresponding difference

in temperature.

For the given example, the heat rise is 22 °C at mid-height in the enclosure.

The internal temperature = external temperature + heat rise

= 35 °C + 22 °C = 57 °C

57 °C < 60 °C stipulated by the standard, i.e. the result is acceptable for an IP3

cubicle.

This gives roughly:

Internal temperature = 60 °C at mid-height in the enclosure for a low IP value.

= 70 °C at mid-height in the enclosure for a high IP value.

Additional information

Thermal characteristics

Thermalmanagement

of switchboards

Example

DD382423.eps