Table of Contents Table of Contents
Previous Page  17 / 210 Next Page
Information
Show Menu
Previous Page 17 / 210 Next Page
Page Background

17

... up to 630 A

The kit concept makes handling and transport

easier and you get to benefit from Schneider

Electric’s efficient international logistics. Your

distributor, hand-picked by Schneider Electric,

can give you the very best advice.

PD390227_SE_2013.eps

System design has been validated by type tests as per standard

IEC 61439-1 & 2 and benefits from the combined experience of

Schneider Electric over many years.

Mechanical characteristics

Electrical switchboards built using thePrisma functional systemand

Schneider Electric recommendations fully complywith international standard

IEC 61439-1&2.

b

b

Steel sheet metal

b

b

Electrophoresis treatment + hot-polymerised

polyester epoxy powder, white colour RAL 9001.

b

b

Enclosures supplied in kit form, totally

dismountable, designed to be assembled and wired

horizontally on a work station.

b

b

Can be combined side by side and one on top of

another

b

b

Degree of protection:

v

IP30: with or without door

v

IP31: with door + canopy

v

IP43: with door + gasket + canopy

v

IP55: IP55 Prisma G offer, supplied in kit form

b

b

degree of protection against mechanical impacts:

v

IK07: without door

v

IK08: with door (plain or transparent)

v

IK10: for Prisma G IP55

b

b

Enclosure dimensions:

v

3 widths:

-- L = 300: duct

-- L = 600: Wall-mounted and floor-standing

enclosures, 24 modules width

-- L = 850: Floor-standing enclosure, 33 modules

height, 36 modules width

v

depth with door:

-- enclosures G IP30: 250 mm

-- enclosures G IP55: 260 mm

v

heights:

-- Prisma G IP30: 11 heights: 330 mm to 1830 mm

-- Prisma G IP55: 7 heights: 450 mm to 1750 mm

b

b

Inside switchboards.

Electrical characteristics

Comply with IEC 62208 and EN 62208 standards:

b

b

rated insulation of main busbars at rear

of enclosure: 1000 V

b

b

I

nA:

630 A

b

b

rated peak withstand current Ipk: 53 kÂ

b

b

rated short-time withstand current Icw:

25 kA rms / 1 second

b

b

short-circuit current: 50 kA

b

b

frequency: 50/60 Hz.