Two solutions are available for remote operation of

Masterpact devices:

b

a point-to-point solution

b

a bus solution with the COM communication option.

The remote ON / OFF function is used to remotely open and close the circuit breaker.

It is made up of:

an electric motor MCH equipped with a “springs charged” limit switch contact CH

b

b

two voltage releases:

b

b

a closing release XF

v

v

an opening release MX.

v

v

Optionally, other functions may be added:

a “ready to close” contact PF

b

b

an electrical closing pushbutton BPFE

b

b

remote RES following a fault.

b

b

A remote-operation function is generally combined with:

device ON / OFF indication OF

b

b

“fault-trip” indication SDE.

b

b

Wiring diagram of a point-to-point remote ON / OFF function

PB104349A68

Note:

an opening order always takes priority over a closing

order.

If opening and closing orders occur simultaneously, the

mechanism discharges without any movement of the main

contacts. The circuit breaker remains in the open position

(OFF).

In the event of maintained opening and closing orders, the

standard mechanism provides an anti-pumping function by

blocking the main contacts in open position.

Anti-pumping function. After fault tripping or intentional

opening using the manual or electrical controls, the closing

order must first be discontinued, then reactivated to close the

circuit breaker.

When the automatic reset after fault trip (RAR) option is

installed, to avoid pumping following a fault trip, the automatic

control system must take into account the information supplied

by the circuit breaker before issuing a new closing order or

blocking the circuit breaker in the open position (information on

the type of fault, e.g. overload, short-time fault, earth fault,

earth leakage, short-circuit, etc.).

Note:

MX communicating releases are of the impulse type

only and cannot be used to lock a circuit breaker in OFF

position. For locking in OFF position, use the remote tripping

function (2nd MX or MN).

When MX or XF communicating releases are used, the third

wire (C3, A3) must be connected even if the communication

module is not installed. When the control voltage (C3-C1 or

A3-A1) is applied to the MX or XF releases, it is necessary to

wait 1.5 seconds before issuing an order. Consequently, it is

advised to use standard MX or XF releases for applications

such as source-changeover systems.

 DB111783

Wiring diagram of a bus-type remote ON / OFF function

DB402067

COM

Remote operation

Remote ON / OFF