Table of Contents Table of Contents
Previous Page  55 / 182 Next Page
Information
Show Menu
Previous Page 55 / 182 Next Page
Page Background

version: 10.1

207E2300.indd

A-41

DB126650

Micrologic 5.0P

Micrologic 6.0E

40

100

%

%

.

.

.

.

.

.

.

.

.

.

.

.

. .

.

.

Reset button for

mechanical

trip indication.

OFF pushbutton.

OFF position lock.

Electrical closing

pushbutton.

ON pushbutton.

Springs charged

indication.

Pushbutton locking.

Contact position

indication.

Operation counter.

PB100811-32

Pushbutton locking VBP

The transparent cover blocks access to the pushbuttons used to open and close the

device.

It is possible to independently lock the opening button and the closing button.

The locking device is often combined with a remote operating mechanism.

The pushbuttons may be locked using either:

three padlocks (not supplied)

b

b

lead seal

b

b

two screws.

b

b

Device locking in the OFF position

VCPO by padlocks, VSPO by keylocks

The circuit breaker is locked in the OFF position by physically maintaining the

opening pushbutton pressed down:

using padlocks (one to three padlocks, not supplied), shackle diameter: 5 to 8 mm

b

b

using keylocks (one or two different keylocks, supplied).

b

b

Keys may be removed only when locking is effective (Profalux or Ronis type locks).

The keylocks are available in any of the following configurations:

one keylock

b

b

one keylock mounted on the device + one identical keylock supplied separately for

b

b

interlocking with another device

two different key locks for double locking.

b

b

Profalux and Ronis keylocks are compatible with each other.

A locking kit (without locks) is available for installation of one or two keylocks (Ronis,

Profalux, Kirk or Castell).

Accessory-compatibility

For Masterpact NT: 3 padlocks or 1 keylock

For Masterpact NW: 3 padlocks and/or 2 keylocks

Cable-type door interlock IPA

This option prevents door opening when the circuit breaker is closed and prevents

circuit breaker closing when the door is open.

For this, a special plate associated with a lock and a cable is mounted on the right

side of the circuit breaker.

With this interlock installed, the source changeover function cannot be implemented.

Access to pushbuttons protected by transparent cover.

PB100810-32

Pushbutton locking using a padlock.

PB100812-32

OFF position locking using a padlock.

PB104365A40

OFF position locking using a keylock.

Locking

On the device