version: 10.1
207E2300.indd
A-30
All the Masterpact devices can be fitted with the
communication function thanks to the COM option.
Masterpact uses the Modbus communications protocol
for full compatibility with the supervision management
systems. An external gateway is available for
communication on other networks:
Eco COM is limited to the transmission of metering
data.
It is not used to communicate status and controls.
For fixed devices, the COM option is made up of:
a Modbus BCM ULP “device” communication module, installed behind the
b
b
Micrologic control unit and supplied with its set of sensors (OF, SDE ,PF and CH
micro switches) its kit for connection to XF and MX1 communicating voltage releases
and its COM terminal block (inputs E1 to E6).
For drawout devices, the COM option is made up of:
a Modbus BCM ULP “device” communication module, installed behind the
b
b
Micrologic control unit and supplied with its set of sensors (OF, SDE, PF and CH
micro switches) its kit for connection to XF and MX1 communicating voltage releases
and its COM terminal block (inputs E1 to E6).
a “chassis” communication module supplied separately with its set of sensors (CE,
b
b
CD and CT contacts) Modbus CCM.
Status indication by the COM option is independent of the device indication contacts.
These contacts remain available for conventional uses.
Modbus BCM ULP “Device” communication module
This module is independent of the control unit. It receives and transmits information
on the communication network. An infra-red link transmits data between the control
unit and the communication module.
Consumption: 30 mA, 24 V.
Modbus CCM “chassis” communication module
This module is independent of the control unit. With Modbus “chassis”
communication module, this module makes it possible to address the chassis and to
maintain the address when the circuit breaker is in the disconnected position.
Consumption: 30 mA, 24 V.
XF and MX1 communicating voltage releases
The XF and MX1 communicating voltage releases are equipped for connection to
the “device” communication module.
The remote-tripping function (MX2 or MN) are independent of the communication
option. They are not equipped for connection to the “device” communication module.
CCM
Modbus BCM ULP “Device” communication module.
1
: Hard wire.
Modbus CCM “Chassis” communication module (option).
2
: Modbus.
OF, SDE, PF and CH micro switches.
3
CE, CD and CT contacts.
4
XF and MX1 communicating voltage releases.
5
Micrologic control unit.
6
COM terminal block (E1 to E6).
7
PB106674-20
Modbus BCM ULP “device”
communication module.
DB402049
PB100802B-27
Modbus CCM “chassis”
communication module.
Functions
and characteristics
Communication
COM option in Masterpact