A-74

Functions and

characteristics

Accessories and auxiliaries

Selection of auxiliaries

for Compact NSX100/160/250

Standard

All Compact NSX100/160/250 circuit breakers and switch-disconnectors have slots

for the electrical auxiliaries listed below.

5 indication contacts

(see page A-80)

2 ON/OFF (OF1 and OF2)

b

1 trip indication (SD)

b

1 fault-trip indication (SDE)

b

1 earth-fault indication (SDV), when the device is equipped with a Vigi module.

b

1 remote-tripping release

(see page A-83)

either 1 MN undervoltage release

b

or 1 MX shunt release.

b

Remote indications

Circuit breakers equipped with Micrologic trip units may be equipped with a fault-trip

indication to identify the type of fault by installing:

1 indication module with two outputs

(see page A-81)

either an SDx module with Micrologic 2.2 / 5.2 A or E / 6.2 A or E

b

or an SDTAM module with Micrologic 2.2 M or 6-2 E-M (motor protection).

b

This module occupies the slots of one OF contact and an MN/MX release.

All these auxiliaries may be installed with a motor mechanism or a rotary

handle.

The following table indicates auxiliary possibilities depending on the type of trip unit.

NA, TMD, TMG, MA

Standard

DB115583

OF1

S

D

OF

2

S

DE

S

D

V

Motor

m

ech

a

nis

m

/

rot

a

ry h

a

ndle

MN /

M

X

DB111392

S

D

OF1

OF

2

S

D

V

S

DE

MN /

M

X

Micrologic 2 / 5 / 6

Standard

Remote indications via SDx or SDTAM

DB115584

OF1

S

D

OF

2

S

DE

Motor

m

ech

a

nis

m

/

rot

a

ry h

a

ndle

MN /

M

X

DB115585

S

Dx /

S

DT

A

M

Motor

m

ech

a

nis

m

/

rot

a

ry h

a

ndle

2

4

V

DC

supply ter

m

in

a

l bloc

k

The SDx or SDTAM uses the OF1 and MN/MX slots.

External connection is made via a terminal block in the OF1 slot.

The 24 V DC supply provides for the Micrologic 5 / 6 display when the device is OFF or under

low-load conditions.