A-70

Functions and

characteristics

Accessories and auxiliaries

&RQQHFWLRQ RI ¿[HG GHYLFHV

Front connection

Bars or cables with lugs

Standard terminals

Compact NSX100 to 630 come with terminals comprising snap-in nuts with screws:

Compact NSX100: M6 nuts and screws. Compact NSX160/250: M8 nuts and

b

screws

Compact NSX400/630: M10 nuts and screws.

b

These terminals may be used for:

direct connection of insulated bars or cables with lugs

b

terminal extensions offering a wide range of connection possibilities.

b

Interphase barriers or terminal shields are recommended. They are mandatory for

certain connection accessories (in which case the interphase barriers are provided).

Bars

:KHQ WKH VZLWFKERDUG FRQ¿JXUDWLRQ KDV QRW EHHQ WHVWHG LQVXODWHG EDUV DUH

mandatory.

Maximum size of bars

Compact NSX circuit breaker

100/160/250

400/630

Without spreaders

pitch (mm)

35

45

maximum bar size (mm)

20 x 2

32 x 6

With spreaders

pitch (mm)

45

52.5

maximum bar size (mm)

32 x 2

40 x 6

Crimp lugs

There are two models, for aluminium and copper cables.

It is necessary to use narrow lugs, compatible with device connections. They must

be used with interphase barriers or long terminal shields. The lugs are supplied with

interphase barriers and may be used for the types of cables listed below.

Cable sizes for connection using lugs

Compact NSX circuit breaker

100/160/250

400/630

Copper cables

size (mm²)

120, 150, 180 240, 300

crimping

hexagonal barrels or punching

Aluminium cables

size (mm²)

120, 150, 180 240, 300

crimping

hexagonal barrels

Terminal extensions

Extensions with anti-rotation ribs can be attached to the standard terminals to

provide numerous connection possibilities in little space:

straight terminal extensions

b

right-angle terminal extensions

b

edgewise terminal extensions

b

double-L extensions

b

45° extensions.

b

Spreaders

Spreaders may be used to increase the pitch:

NSX100 to 250: the 35 mm pitch can be increased to 45 mm

b

NSX400/630: the 45 mm pitch can be increased to 52 or 70 mm.

b

Bars, cable lugs or cable connectors can be attached to the ends.

One-piece spreader for NSX100 to 250

Connection of large cables may require an increase in the distance between the

device terminals.

The one-piece spreader is the means to:

increase the 35 mm pitch of the NSX100 to 250 circuit-breaker terminals to the

b

45 mm pitch of a NSX400/630 device

use all the connection and insulation accessories available for the next largest

b

frame size (lugs, connectors, spreaders, right-angle and edgewise terminal

extensions, terminal shields and interphase barriers).

It may also be used for Interpact INS switch-disconnectors.

Equipped with a single-piece spreader, Compact NSX devices can be mounted:

at the back of a switchboard

b

behind the front panel with a raiser.

b

The one-piece spreader is also the means to:

align devices with different frame sizes in the switchboard

b

use the same mounting

b

plate, whatever the device.

Pitch (mm) depending on the type of spreader

Compact NSX circuit breaker

NSX100 to 250 NSX400 to 630

Without spreaders

35

45

With spreaders

45

52.5 or 70

With one-piece spreader

45

-

)L[HG FLUFXLW EUHDNHUV DUH GHVLJQHG IRU

standard front connection using bars or

cables with lugs.

Cable connectors are available for bare

cables. Rear connection is also possible.

DB112168

DB112169

Insulated bar.

DB112170

Small lug for copper cables.

DB112171

Small lug for Al cables.

DB112172

DB112173

DB112174

Straight terminal

H[WHQVLRQV

Right-angle terminal

H[WHQVLRQV

ƒ WHUPLQDO

H[WHQVLRQV

DB112175

DB112176

DB112177

Edgewise terminal

H[WHQVLRQV

Double-L terminal

H[WHQVLRQV

Spreaders.

DB112181

DB112179

DB112180

Mounting at the

back of a

switchboard.

Mounting

behind the front

panel with a

raiser.