Functions and

characteristics

Power Meter functions

Electronic Micrologic 5 / 6 A or E

In addition to protection functions,

Micrologic 5 / 6 trip units offer all the

functions of Power Meter products as well

as operating-assistance for the circuit

breaker.

b

display of settings

b

measurement functions:

v

Ammeter (A)

v

Energy (E)

b

alarms

b

time-stamped histories and event tables

b

maintenance indicator

b

communication.

Micrologic A and E measurement functions are made possible by Micrologic

intelligence and the accuracy of the sensors. They are handled by a microprocessor

that operates independent of protection functions.

Display

..................................................................

Micrologic LCD

The user can display all the protection settings and the main measurements on the

LCD screen of the trip unit.

Micrologic A: instantaneous rms current measurements

b

Micrologic E: voltage, frequency and power measurements and energy metering,

b

in addition to the measurements offered by Micrologic A

To make the display available under all conditions and increase operating comfort,

DQ H[WHUQDO SRZHU VXSSO\ LV UHFRPPHQGHG IRU 0LFURORJLF $

It is indispensable to:

display faults and interrupted current measurements

b

use all the functions of Micrologic E (e.g. metering of low power and energy

b

values)

ensure operation of the communication system.

b

7KH H[WHUQDO SRZHU VXSSO\ FDQ EH VKDUHG E\ VHYHUDO GHYLFHV )RU GHVFULSWLRQ

see

SDJH $

.

FDM121 display unit

An FDM121 switchboard display unit can be connected to a Micrologic trip unit using

a prefabricated cord to display all measurements on a screen. The result is a

YHULWDEOH [ PP 3RZHU 0HWHU

In addition to the information displayed on the Micrologic LCD, the FDM121 screen

VKRZV GHPDQG SRZHU TXDOLW\ DQG PD[LPHWHU PLQLPHWHU YDOXHV DORQJ ZLWK DODUPV

histories and maintenance indicators.

The FMD121 display unit requires a 24 V DC power supply. The Micrologic trip unit is

supplied by the same power supply via the cord connecting it to the FDM121.

PC screen

When the Micrologic, with or without an FDM121 switchboard display unit, is

FRQQHFWHG WR D FRPPXQLFDWLRQ QHWZRUN DOO LQIRUPDWLRQ FDQ EH DFFHVVHG YLD D 3&

Measurements

.....................................................

Instantaneous rms measurements

The Micrologic A and E continuously display the RMS value of the highest current of

WKH WKUHH SKDVHV DQG QHXWUDO ,PD[ 7KH QDYLJDWLRQ EXWWRQV

can be used to

scroll through the main measurements.

In the event of a fault trip, the current interrupted is memorised.

The Micrologic Ameasures phase, neutral, ground fault currents.

The Micrologic E offers voltage, frequency and power measurements in addition to

the measurements provided by Micrologic A

Maximeters / minimeters

Every instantaneous measurement provided by Micrologic A or E can be associated

ZLWK D PD[LPHWHU PLQLPHWHU 7KH PD[LPHWHUV IRU WKH KLJKHVW FXUUHQW RI WKH SKDVHV

and neutral, the demand current and power can be reset via the trip unit keypad, the

FDM121 display unit or the communication system.

Energy metering

The Micrologic E also measures the energy consumed since the last reset of the

meter. The active energy meter can be reset via the keypad and the FDM121 display

unit or the communication system.

Demand and maximum demand values

Micrologic E also calculates demand current and power values. These calculations

can be made using a block or sliding interval that can be set from 5 to 60 minutes in

steps of 1 minute. The window can be synchronised with a signal sent via the

communication system. Whatever the calculation method, the calculated values can

EH UHFRYHUHG RQ D 3& YLD 0RGEXV FRPPXQLFDWLRQ

Ordinary spreadsheet software can be used to provide trend curves and forecasts

based on this data. They will provide a basis for load shedding and reconnection

operations used to ad

j

ust consumption to the subscribed power.

Power quality

Micrologic E calculates power quality indicators taking into account the presence of

harmonics up to the 15th order, including the total harmonic distortion (THD) of

current and voltage.

3%

Micrologic built-in LCD display showing an energy

measurement.

DB112211

A

l

a

r

m

s

S

ervices

E

S

C

OK

M

a

in Menu

Quic

k V

ie

w

Meterin

g

FDM121 display: navigation.

'%

I1

I

%

3

10 A I2

%

3

15 A

I

3

%

3

02 A IN

%

2

3

A

E

S

C

'%

E

S

C

U

1

U

2

U

3

V

4/

7

402 V

100 120

%

3

98 V

100 120

%

401 V

100 120

%

Current.

Voltage.

'%

E

S

C

P

6

4

k

W

Q

38

kVa

r

S

51

kVA

PQ

S

'%

E

S

C

Ep

1439

7 k

Wh

E

q

83

2

5

kVa

rh

Es

13035

kVA

h

E

Power.

Consumption.

Examples of measurement screens on the FDM121 display

unit.

A-20