Technical data
Main characteristics
Insulation voltage (Ui)
500 V
Pollution degree
3
Rated impulse withstand voltage (Uimp)
6 kV
According to IEC/EN 61008-1
Making and breaking capacity (Im/I
D
m)
1500 A
Surge current
withstand (8/20 μs)
without tripping
AC and A types (no selective
s
) 250 Â
AC, A types (selective
s
)
3 kÂ
SI
type
3 kÂ
Conditional rated
short circuit current
(Inc/I
D
c)
With iC60N/H/L
Equal to breaking capacity of iC60
With fuse
10,000 A
Additional characteristics
Degree of protection Device only
IP20
Device in modular enclosure IP40
Insulation classe II
Endurance (O-C)
Electrical (AC1) 16 to 63 A 15,000 cycles
80 to 100 A 10,000 cycles
Mechanical
20,000 cycles
Operating
temperature
AC type
-5°C to +60°C
A and
SI
types
-25°C to +60°C
Storage temperature
-40°C to +85°C
iID residual current
circuit breakers (AC, A,
SI
types)
Connection
Without accessory With accessories*
DB122947
Type Tightening
torque
Copper cables
50 mm²
Al
terminal
Screw-on
connection
for ring
terminal
Multi-cables terminal
Rigid
Flexible
or ferrule
Rigid
cables
Flexible
cables
iID
3.5 N.m 1 to 35 mm
2
1 to 25 mm
2
50 mm
2
Ø 5 mm
3 x 16 mm
2
3 x 10 mm
2
DB122945
DB122946
PZ2
14 mm
DB122935
DB118789
DB118787
Protection
Earth leakage protection
6.5 mm
DB123310
DB123312
Clip on DIN rail 35 mm.
Indifferent position of installation.
DB123314
IP20
IP40