1/5
Acti 9 Isobar
A type distribution boards (cont.)
Distribution boards
Technical
Section 11
Dimensions
Section 12
1
Technical data Standard, Meter ready, Split metered Acti 9 Isobar
Main characteristics
110v
230/240v
According to BE EN 61439-3
Withstand
conditional
25kA
25kA
unconditional
25kA/50mS
25kA/50mS
17kA/200mS
17kA/200mS
insulation voltage (Ui)
500V
500V
Pollution degree
3
3
Rated inpulse withstand voltage (Uimp)
6kV
6kV
Current rating (A)
direct connection
125A
Terminal block
125A
Switch disconnector
125A
Power switch
125A
RCCB
sensitivites (mA)
30, 100, 300, 300TD, 100A
Degree of protection
External IP3X
(IEC 60529)
Internal IP20
Endurance (O-C) Isobar switch
disconnector
3000
Overvoltage category
IV
Operating temperature
-35 to +70
0
C
Storage teperature
-40 to +80
0
C
Connections
Rating
Tightening torque
Copper lugs
Cables bare
Device
125 amp
b
b
50mm
DIN switch disconnector
125 amp
b
b
50mm
Terminal block
100 amp
b
b
35mm
RCCB
125 amp rated bars with
non removable covers
fully insulated
construction
Acti 9 Isobar Dual supply distribution boards busbar rating 125 amp
Incomers not included
Section 1 SP ways Section 2 SP ways
SEA9AN106DS
10
6
SEA9AN26DS
2
6
SEA9AN66DS
6
6
Acti 9 Isobar Split metered distribution boards busbar rating 100 amp
direct connected meters
Incoming switch disconnector
included Meter type
No of SP ways
No of SP ways
SEA9AN6S6
40A direct connected 6
6
SEA9AN10S10 63A direct connected 10
10
SEA9AN14S14 63A direct connected 14
14
padlockable in the off
position only
switch disconnector for
each outgoing way
Total load
2 row 50A per row
1 row 40A per split
Meter used
A9M17067
A9MEM2010
SEA9AN10S10