Background Image
Table of Contents Table of Contents
Previous Page  9 / 408 Next Page
Information
Show Menu
Previous Page 9 / 408 Next Page
Page Background

1/5

Acti 9 Isobar

A type distribution boards (cont.)

Distribution boards

Technical

Section 11

Dimensions

Section 12

1

Technical data Standard, Meter ready, Split metered Acti 9 Isobar

Main characteristics

110v

230/240v

According to BE EN 61439-3

Withstand

conditional

25kA

25kA

unconditional

25kA/50mS

25kA/50mS

17kA/200mS

17kA/200mS

insulation voltage (Ui)

500V

500V

Pollution degree

3

3

Rated inpulse withstand voltage (Uimp)

6kV

6kV

Current rating (A)

direct connection

125A

Terminal block

125A

Switch disconnector

125A

Power switch

125A

RCCB

sensitivites (mA)

30, 100, 300, 300TD, 100A

Degree of protection

External IP3X

(IEC 60529)

Internal IP20

Endurance (O-C) Isobar switch

disconnector

3000

Overvoltage category

IV

Operating temperature

-35 to +70

0

C

Storage teperature

-40 to +80

0

C

Connections

Rating

Tightening torque

Copper lugs

Cables bare

Device

125 amp

b

b

50mm

DIN switch disconnector

125 amp

b

b

50mm

Terminal block

100 amp

b

b

35mm

RCCB

125 amp rated bars with

non removable covers

fully insulated

construction

Acti 9 Isobar Dual supply distribution boards busbar rating 125 amp

Incomers not included

Section 1 SP ways Section 2 SP ways

SEA9AN106DS

10

6

SEA9AN26DS

2

6

SEA9AN66DS

6

6

Acti 9 Isobar Split metered distribution boards busbar rating 100 amp

direct connected meters

Incoming switch disconnector

included Meter type

No of SP ways

No of SP ways

SEA9AN6S6

40A direct connected 6

6

SEA9AN10S10 63A direct connected 10

10

SEA9AN14S14 63A direct connected 14

14

padlockable in the off

position only

switch disconnector for

each outgoing way

Total load

2 row 50A per row

1 row 40A per split

Meter used

A9M17067

A9MEM2010

SEA9AN10S10