Background Image
Table of Contents Table of Contents
Previous Page  7 / 408 Next Page
Information
Show Menu
Previous Page 7 / 408 Next Page
Page Background

1/3

Acti 9 Isobar

B type 3 phase

distribution boards

Features

Technical

Section 11

Dimensions

Section 12

1

b

b

Fully type tested conditional short circuit rating of 25kA to BS EN 61439-3

b

b

High performance MCB 10kA BS EN 60898 15kA BS EN 60947-2 in B, C or D

curve 1, 2, 3, 4 pole

b

b

250A busbar rating

b

b

Isobar disconnection to BS EN 60947-3 ensuring unused outgoing ways are

isolated

b

b

Option of switching outgoing neutral on all boards using distributed neutral kit

b

b

Terminal block for feeding up to 100A

b

b

Range of incomers: switch disconnectors, residual current devices, terminal

blocks, mccb

b

b

Single pole RCBO for new or retrofit maintaining device density

b

b

Full range of device accessories and auxiliaries

b

b

Knockouts for cable gland and conduit mixed to suit the installation needs

without loss of space

b

b

Removable insulated pan assembly

b

b

Fully shrouded neutral

b

b

Split neutral bars

b

b

Removable gland plates

b

b

Optional metering, dual supply, surge protection and contactor on incoming

b

b

Metered extension enclosures

Fully shrouded

neutral bars

Non removable interlock to

prevent operation unless

an outgoing device is fitted

Fully shrouded

connections when

main switch is fitted

Conversion of any

outgoing way into neutral

Wide range of add-on

auxiliaries, e.g. shunt

trips, auxiliary switches,

add-on earth leakage

modules, etc

Standard, meter ready,

split metered and multi

service options

Fully encapsulated busbar

system

Wide range of

incomers