Kaedra

Enclosures and mini

enclosures for modular

switchgear

A few tricks

4

3

2

1

Add-on possibility

Enclosures can be

horizontally or vertically

associated keeping

the IP65 and allowing

cable insertion.

Dovetails

Arranged on the back and

on the chassis, they can

accommodate:

b

b

4-hole terminal blocks

b

b

wiring straps.

Back/front

face hinges

Clipped onto the right or

left, they simplify cabling

and working on the

interface zone.

Chassis

b

b

DIN symmetrical rails

positionable in 2 depths

and 2 heights to privilege

cabling room

b

b

Chassis that can be

severed to install a

mounting plate on the

back

Marking

Clip-on label covers ensure

neat, quick and upgradeable

marking.

Mechanical data

Enclosure

b

b

Reversible front face for opening of door to the left or right

b

b

Inside depth available for installation of non-modular switchgear between the

slotted mounting plate and the plain front plate: 100 mm

b

b

Reversible front plate according to distance between axes of rails

(125, 150, 175 mm)

Mini enclosure

b

b

Clip-on terminal block support

b

b

Back with dovetail to accommodate 4-hole terminal block and wiring strap.

Technical data

b

b

Self-extinguishing insulating material

b

b

Operating temperature: -25 °C to +60 °C

b

b

Colour: light grey RAL 7035 and transparent green door

b

b

IP65 as per IEC 60529

b

b

IK09 as per EN 50102

b

b

Class 2: total insulation

b

b

Flame and abnormal heat resistance: 650 °C as per IEC 60695-2-1

b

b

Complies with standard IEC 60439-3

b

b

Resistance to chemicals and atmospherics agents: see PAGE 93140.