7

MIN, MINs, MINp and MINt (cont.)

Timers

MINp

MINt

Accessory

Silent electronic timer

Wall mount accessory

The MINp timer allows closing and then opening of a contact

in a determined time, and it also provides warning that the

lighting is about to be switched off by flickering of the

lamplight (switch-off warning)

The MINt timer is the same as MINp with an "impulse relay"

additional function

The MIN timers can be

mounted on a wall by using

15359 reference.

The protection cover is sealable.

4 N

L 3

R

4 wires

or

3 wires

4 N

L 3

R

4 wires

or

3 wires

The 15359 accessory can be

also used to mount others

18 mm DIN rail devices

(for example: time switches,

circuit breakers...).

b

b

Time delay adjustable from 0.5 to 20 min.

b

b

Three operating modes triggered by switch on front face:

v

v

timer mode with "switch-off warning" function built into the device. The lamp blinks 40 and 30 s before the end of the time delay

v

v

timer mode mode without "switch-off warning" function

v

v

permanent mode : constant lighting

b

b

Timer mode operation:

v

v

pressing a push-button for longer than 2 s: lighting will

last for 1 h. Pressing again a push-button for less than 2 s

relaunch the time delay of 1 h and pressing again a

push-button for more than 2 s switches off the light

v

v

pressing a push-button for less than 2 s launch the

pre-set time delay, pressing again a push-button for less

than 2 s relaunch the pre-set time delay

b

b

Timer mode operation:

v

v

pressing a push-button for longer than 2 s: lighting will last

for 1 h. Pressing again a push-button for less than 2 s relaunch

v

v

the time delay of 1 h and pressing again a push-button

for more than 2 s switches off the light

v

v

pressing a push-button for less than 2 s launch the pre-set

time delay, pressing again a push-button for less than 2 s,

switches off the light (impulse relay mode)

CCT15233

CCT15234

15359

230 V AC, 50/60 Hz

230 V AC, 50/60 Hz

< 6 VA

< 6 VA

16 A

16 A

IP20B

IP20B

-25°C to +50°C

-25°C to +50°C

2

2

See § dimensions

150 mA maxi

150 mA maxi

0.5 to 20 min.

0.5 to 20 min.

1 h

1 h

Class II

Class II

b

b

b

b

Automatic

Automatic

b

b

b

b

b

b

b

b

b

b

P111643

P111644

P135159

P106871

P106871