Background Image
Table of Contents Table of Contents
Previous Page  190 / 408 Next Page
Information
Show Menu
Previous Page 190 / 408 Next Page
Page Background

7/58

Technical

Section 11

Dimensions

Section 12

7

Control relays

iRCI

iRCU

Type

Current control

Voltage control

Function

b

b

Monitors the current (Ir) flowing in an AC or DC circuit

and indicates any crossing of the set threshold

b

b

Monitors the voltage variation (Ur) of an AC or DC

circuit and indicates any crossing of the set threshold

Wiring diagrams

L

N

1

7 3 5

2

864

L

N

1

7 3 5

2

864

0.15 A

y

Ir

y

1.5 A

AC/DC

1 A

y

Ir

y

10 A

AC/DC

L

N

1

7 3 5

2

864

L

N

1

7 3 5

2

864

10 V

y

Ur

y

100 V

50 V

y

Ur

y

500 V

Catalogue numbers

A9E21181

A9E21182

Common technical specifications

Supply voltage (Uc)

V AC

230, -15 % to +10 %

Frequency

Hz

50/60

Parameter setting

b

b

On the front panel, by direct scale, using a screwdriver

Precision of display

±10 % of full scale

Output by changeover contact

8 A under 250 V AC (cos

ϕ

= 1)

Indications by LED

Green

Voltage presence

Red

Fault

Consumption

VA

3

Dissipated power

W

2

Degree of protection

Device only IP20

Connection by tunnel terminals Rigid cable 1.5 x 6 mm

2

Width in 9-mm modules

4

Operating temperature

°C

-5 … +55

Storage temperature

°C

-40 … +80

Particular technical specifications

Threshold adjustable from 10 % to 100 % of Ir

Threshold adjustable from 10 % to 100 % of Ur

Hysteresis adjustable from 5 % to 50 % of Ir

Hysteresis adjustable from 5 % to 50 % of Ur

Monitoring of overcurrent and undercurrent (selection by selector switch)

Fail-safe contact

De-energized

2

864

Energized with fault

Energized without fault

2

864

Time delay on crossing threshold: 0.1 s to 10 s

Possibility of memorizing fault with resetting

Compatible with current transformers (CTs) of ratio X/5 b

b

Automatic recognition of AC voltage or DC voltage.

b

b

2 measuring ranges selected by cabling:

v

v

10 V to 50 V

v

v

50 V to 500 V

b

b

Automatic recognition of alternating or direct current.

b

b

2 measuring ranges selected by cabling:

v

v

0.15 A to 1.5 A

v

v

1 A to 10 A

PB107125-35

DB405266

DB405266

PB107126-35

iRCP phase control, iRCI current

control, iRCU voltage control and

iRCC compressor control relays

Monitoring

Control

Remote control