7/25
Technical
Section 11
Dimensions
Section 12
7
iTL impulse relays
Electrical auxiliaries
for iTL impulse relays (cont.)
Remote control
Operation of the iATL24
O/C 24 V DC output
DB124314
T
T
iTL contacts
O/C 24 V DC output
Wiring with exclusive selector 230 V AC and 24 V DC controls
Wiring for non-exclusive 230 V AC and 24 V DC controls
DB124446
In In
Out
24V
Ti24
Y3 24V O/C 0V
P
P
iATL24
DB124447
In In
Out
24V
Ti24
Y3 24V O/C 0V
P
P
iATL24
DB124448
DB124449
Acti 9 Smartlink or PLC
24 V DC
0 V
Acti 9 Smartlink or PLC
24 V DC
0 V
Y1 230 V AC
Y2 230 V AC
Y3 24 V DC
iTL status
Y1 230 V AC
Y2 230 V AC
Y3 24 V DC
iTL status
Parameter
Min
Max
T Time delay between iATL24 closing and indication
100 ms 200 ms
b
b
Minimum duration of 230 V AC pulse (Y2): 200 ms.
b
b
30 iATL24 closing or opening actuations are authorized per minute: Minimum time
delay between 2 actuations on the iATL24 via Y1,Y2, Y3 (closing or opening of the
iTL coil): 440 ms.
b
b
10 closing or opening actuations spaced 440 milliseconds apart are authorized
following no loading of the iATL24 during a period of 20 seconds.