7/21

Technical

Section 11

Dimensions

Section 12

7

iTL impulse relays (cont.)

Remote control

DB123623

Operation

Switch set to auto

Switch set to OFF

DB123309

DB123311

Clip on DIN rail 35 mm.

Indifferent position of installation.

DB123313

IP20

IP40

Technical data

Control circuit

iTL and iTLI 16 A

iTLc, iTLm, iTLs,

iETL 16 A

iTL 32 A,

iETL 32 A

Dissipated power (during the impulse)

1, 2, 3P: 19 VA

19 VA

4P: 38 VA

Illuminated PB control

Max. current 3 mA (if > use an ATLz)

Operating threshold

Min. 85 % of Un in conformance with

IEC/EN60669-2-2

Duration of the control order

50 ms to 1 s (200 ms recommended)

Response time

50 ms

Power circuit

Voltage rating (Ue)

1P, 2P

24 ...250 V AC

3P, 4P

24....415 V AC

Frequency

50 Hz or 60 Hz

Maximum number of operations per minute

5

Maximum number of switching operation a day 100

Additional characteristics to IEC/EN 60947-3

Insulation voltage (Ui)

440 V AC

Pollution degree

3

Rated impulse withstand voltage (Uimp)

6 kV

Endurance (O-C)

Electrical to IEC/EN 60947-3

200,000 cycles (AC21) 50,000 cycles (AC21)

100,000 cycles (AC22) 20,000 cycles (AC22)

Overvoltage category

IV

Other characteristics

Degree of protection

(IEC 60529)

Device only

IP20

Device in modular

enclosure

IP40

Insulation class II

Operating temperature

-20°C to +50°C

Storage temperature

-40°C to +70°C

Tropicalization (IEC 60068-1)

Treatment 2 (relative humidity 95 % at 55°C)