Air-water exchangers

ClimaSysCE

Thermal management system

Characteristics

Characteristics

Side-mounting models 

Available in two installation versions: Top-mounting model and side-mounting model.

Main components: thermostat adjustment system, Exchange cassette, fans for internal circuits of the enclosure,

protection device against possible leaks.

Eyebolts included in all models.

Material

RAL 7035 grey painted zinc-coated steel or stainless steel

Certifications

b

b

CE declaration

b

b

UL (only references ending with UL)

Installation

Indoor

Cooling characteristics

Cooling power W10A35

1000 W

1750 W

2500 W

3500 W

4500 W

Hydraulic circuit maximum

pressure

5 bar

5 bar

5 bar

5 bar

5 bar

Air flow of the external circuit

(ambient)

330 m³/h

570 m³/h

860 m³/h

1050 m³/h

1450 m³/h

Thermostat type

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

Temperature setting range

+20 … +46°C

+20 … +46°C

+20 … +46°C

+20 … +46°C

+20 … +46°C

Temperature range external

circuit (ambient)

+1 … +70°C

+1 … +70°C

+1 … +70°C

+1 … +70°C

+1 … +70°C

Type of fluid

Filtered water or

glicolised water

Filtered water or

glicolised water

Filtered water or

glicolised water

Filtered water or

glicolised water

Filtered water or

glicolised water

Water flow

150 l/h

150 l/h

500 l/h

500 l/h

500 l/h

Pressure drop

0.1 bar

0.1 bar

0.3 bar

0.2 bar

0.2 bar

Hydraulic connection

1/2" G

3/4" G

3/4" G

3/4" G

3/4" G

Electric characteristics

Input voltage

1 x 230 V / 50-60 Hz*

1 x 230 V / 50-60 Hz*

1 x 230 V / 50-60 Hz*

1 x 230 V / 50-60 Hz*

1 x 230 V / 50-60 Hz*

Rated Intensity

0.17 A

0.36 A

0.33 A

0.55 A

0.71 A

Power consumption absorved

W10A35

29 W

75 W

80 W

130 W

160 W

Thermal protection

recommended (fuse)

T2 A

T2 A

T2 A

T2 A

T2 A

Physical characteristics

External dimensions (H x W x D) 450 x 310 x 115 mm 901 x 398 x 137 mm 901 x 398 x 137 mm 1148 x 398 x 163 mm 1148 x 398 x 163 mm

Protection degree IP internal /

external

IP55 / IP55

IP55 / IP55

IP55 / IP55

IP55 / IP55

IP55 / IP55

Noise level

55 dB (A)

58 dB (A)

58 dB (A)

64 dB (A)

69 dB (A)

Weight of unit

12 kg

18 kg

19 kg

29 kg

30 kg

References

Steel

NSYCEW1K

NSYCEW1K8

NSYCEW2K5

NSYCEW3K5

NSYCEW4K5

Stainless steel

NSYCEWX1K

NSYCEWX1K8

NSYCEWX2K5

NSYCEWX3K5

NSYCEWX4K5

Steel UL

NSYCEW1KUL

NSYCEW1K8UL

NSYCEW2K5UL

NSYCEW3K5UL

NSYCEW4K5UL

Stainless steel UL

NSYCEWX1KUL

NSYCEWX1K8UL

NSYCEWX2K5UL

NSYCEWX3K5UL

NSYCEWX4K5UL