Table of Contents Table of Contents
Previous Page  463 / 576 Next Page
Information
Show Menu
Previous Page 463 / 576 Next Page
Page Background

463

PB501050-44

PB501051-36

PB501052-19

PB501052-19

PB501053-21

ClimaSysCV

Thermal management system

Characteristics

Forced ventilation fan

38 m

3

/h

Forced ventilation fan

85 m

3

/h

Forced ventilation fan

165 m

3

/h

Forced ventilation fan

300 m

3

/h

Forced ventilation fan

560-850 m

3

/h

The fans comprise an axial motor, a protective housing on the front and rear surfaces and a filter designed to retain dust particles.

This filter can be replaced during operation without risk of contact with the rotating element.

Injected thermoplastic (ASA PC). self-extinguishing according to UL 94 V-0

RAL 7035 as standard, with the option of RAL 7032

b

b

The outside temperature (Te) must be 5°C lower than the desired temperature (Ts) inside the enclosure

b

b

The filters that equip the fans must be cleaned and replaced regularly

b

b

The surrounding environment must be relatively clean and overfrequent filter replacement should be avoided

b

b

Bear in mind the pressure losses caused by the outlet element (grille with filter, ventilation louvre or simple opening) when determining the fan flow rate

b

b

Storage Temperature: -40…+ 70°C

IP54

The cut-out template supplied with the device avoids the need for marking and protects the surface of the enclosure during handling

The device can be equipped with a filter that provides even more efficient protection for your sensitive facilities against dust particles

References

NSYCVF38M230PF

*

-

-

-

-

NSYCVF38M115PF

*

-

-

-

-

NSYCVF38M24DPF

-

-

-

-

NSYCVF38M48DPF

-

-

-

-

-

NSYCVF85M230PF

-

-

-

-

NSYCVF85M115PF

-

-

-

-

NSYCVF85M24DPF

-

-

-

-

NSYCVF85M48DPF

-

-

-

-

-

NSYCVF165M230PF

-

-

-

-

NSYCVF165M115PF

-

-

-

-

NSYCVF165M24DPF

-

-

-

-

NSYCVF165M48DPF

-

-

-

-

-

NSYCVF300M230PF

-

-

-

-

NSYCVF300M115PF

-

-

-

-

NSYCVF300M24DPF

-

-

-

-

NSYCVF300M48DPF

-

-

-

-

-

NSYCVF560M230PF

-

-

-

-

NSYCVF560M115PF

-

-

-

-

NSYCVF850M230PF

-

-

-

-

NSYCVF850M115PF

-

-

-

-

NSYCVF850M400PF

* Warning: the fan

NSYCVF38M230PF

&

NSYCVF38M115PF

MUST NOT be connected to a power conversion module, an inverter or UPS type of power supply!