8/16
223
223
248
268
60
50
40
30
20
10
0
40
80 120 160 200
∆Pa
m
3
/h
NSYCVF165M230PF
60 Hz
NSYCAG223LPF
50 Hz
Forced ventilation 165 m
3
/h
General characteristics
● The fans comprise an axial motor, a protective housing on the front and rear
surfaces and a filter designed to retain dust particles.
● This filter can be replaced during operation without risk of contact with the rotating
element.
● Optionally, the device can be equipped with a filter that provides even more
efficient protection for your sensitive facilities against dust particles.
● The cut-out template supplied with the device avoids the need for marking and
protects the surface of the enclosure during the handling.
● RAL 7035 grey in the standard offer with the possibility to change to RAL 7032 by
means of a replacement grille.
Conditions of use
● The outside temperature (Te) must be 5 ºC lower than the desired temperature
(Ts) inside the enclosure.
● The filters that equip the fans must be cleaned and replaced regularly.
● The surrounding environment must be relatively clean and overfrequent filter
replacement should be avoided.
● Bear in mind the pressure losses caused by the outlet element (grille with filter,
ventilation louvre or simple opening) when determining the fan flow rate.
Specifications
Reference
Colour: RAL 7035
NSYCVF165M230PF
NSYCVF165M115PF NSYCVF165M24DPF NSYCVF165M48DPF
Free flow rate with filter (m
3
/h)
165 (50 Hz) 193 (60 Hz)
190 m
3
/h
Flow rate with 1 outlet grille (m
3
/h)
153 (50 Hz) 171 (60 Hz)
171 m
3
/h
Flow rate with 2 outlet grilles (m
3
/h)
161 (50 Hz) 175 (60 Hz)
179 m
3
/h
Nominal voltage
230 V (50/60 Hz)
115 V (50/60 Hz)
24 V DC
48 V DC
Voltage range
175 V...253 V
75 V...126 V
10 V...27,6 V
25 V...55,2 V
Absorbed power
16.3/14.3 W
15.5/14.4 W
8 W
8.7 W
Max. intensity (50/60 Hz)
0.12/0.94 A
0.20/0.18 A
0.3 A
0.18 A
Noise level
50/51 dB (A)
Bearing
Balls
IP
54
External dimensions (mm)
268 248 104
Cut-out (mm)
223 223
Weight
1140 kg
0.810 kg
Material
Injected thermoplastic (ASA PC), self-extinguishing according to UL94 V0
Operating temperature
-20...+60 ºC
-10...+70 ºC
Storage temperature
-40...+70 ºC
Max. static pressure
50 Pa
Dimensions
Flow curves
Flow
Difference of static pressure (Pa)
222.7
119
104 9.5
18
08_016_CV003.indd 16
29/1