Page 598 - 0700-schn-encl-10

Basic HTML Version

8/17
180
150
120
90
60
30
0
60 120 180 240 300 360
∆Pa
m
3
/h
NSYCVF300M230PF
60 Hz
NSYCAG291LPF
50 Hz
248
268
223
223
General characteristics
● The fans comprise an axial motor, a protective housing on the front and rear
surfaces and a filter designed to retain dust particles.
● This filter can be replaced during operation without risk of contact with the rotating
element.
● Optionally, the device can be equipped with a filter that provides even more
efficient protection for your sensitive facilities against dust particles.
● The cut-out template supplied with the device avoids the need for marking and
protects the surface of the enclosure during handling.
● RAL 7035 grey in the standard offer with the possibility to change to RAL 7032 by
means of a replacement grille
Conditions of use
● The outside temperature (Te) must be 5 ºC lower than the desired temperature
(Ts) inside the enclosure.
● The filters that equip the fans must be cleaned and replaced regularly.
● The surrounding environment must be relatively clean and overfrequent filter
replacement should be avoided.
● Bear in mind the pressure losses caused by the outlet element (grille with filter,
ventilation louvre or simple opening) when determining the fan flow rate.
Forced ventilation 300m
3
/h
Specifications
Reference
Colour: RAL 7035
NSYCVF300M230PF
NSYCVF300M115PF NSYCVF300M24DPF NSYCVF300M48DPF
Free flow rate with filter (m
3
/h)
300 (50 Hz) 350 (60 Hz)
262 m
3
/h
Flow rate with 1 outlet grille (m
3
/h)
260 (50 Hz) 307 (60 Hz)
221 m
3
/h
Nominal voltage
230 V (50/60 Hz)
115 V (50/60 Hz)
24 V DC
48 V DC
Voltage range
145 V...253 V
75 V...126 V
12 V...30 V
25 V...60 V
Absorbed power
36/37 W
36/36 W
13 W
11 W
Max. intensity (50/60 Hz)
0.17/0.16 A
0.35/0.32 A
0.53 A
0.24 A
Noise level
55/56 dB (A)
Bearing
Balls
IP
54
External dimensions (mm)
268 248 116
268 248 103,4
Cut-out (mm)
223 223
Weight
1.3 kg
1.1 kg
Material
Injected thermoplastic (ASA PC), self-extinguishing according to UL94 V0
Operating temperature
-10...+70 ºC
-10...+70 ºC
Storage temperature
-40...+70 ºC
Max. static pressure
158 Pa
Dimensions
Flow curves
Flow
Difference of static pressure (Pa)
116 9.5
172
222.7
18
08_017_CV004.indd 17
29/1