Page 596 - 0700-schn-encl-10

Basic HTML Version

8/15
60
50
40
30
20
10
0
20
40
60
80 100
∆Pa
m
3
/h
NSYCVF85M230PF
60 Hz
NSYCAG125LPF
50 Hz
150
170
125
125
Forced ventilation 85 m
3
/h
General characteristics
● The fans comprise an axial motor, a protective housing on the front and rear
surfaces and a filter designed to retain dust particles.
● This filter can be replaced during operation without risk of contact with the rotating
element.
● Optionally, the device can be equipped with a filter that provides even more
efficient protection for your sensitive facilities against dust particles.
● The cut-out template supplied with the device avoids the need for marking and
protects the surface of the enclosure during handling.
● RAL 7035 grey in the standard offer with the possibility to change to RAL 7032 by
means of a replacement grille.
Conditions of use
● The outside temperature (Te) must be 5 ºC lower than the desired temperature
(Ts) inside the enclosure.
● The filters that equip the fans must be cleaned and replaced regularly.
● The surrounding environment must be relatively clean and overfrequent filter
replacement should be avoided.
● Bear in mind the pressure losses caused by the outlet element (grille with filter,
ventilation louvre or simple opening) when determining the fan flow rate.
Specifications
Reference
Colour: RAL 7035
NSYCVF85M230PF
NSYCVF85M115PF
NSYCVF85M24DPF
NSYCVF85M48DPF
Free flow rate with standard filter (m
3
/h)
85 (50 Hz) 98 (60 Hz)
79 (50 Hz) 92 (60 Hz)
80 m
3
/h
Flow rate with 1 outlet grille (m
3
/h)
63 (50 Hz) 72 (60 Hz)
65 (50 Hz) 74 (60 Hz)
60 m
3
/h
Nominal voltage
230 V (50/60 Hz)
115 V (50/60 Hz)
24 V DC
48 V DC
Voltage range
175 V...253 V
75 V...126 V
10 V...27.6 V
25 V...55.2 V
Absorbed power
17/15 W
16/15 W
7.6 W
8 W
Max. intensity (50/60 Hz)
0.121/0.097 A
0.207/0.179 A
0.30 A
0.173 A
Noise level
46/49 dB (A)
Bearing
Balls
IP
54
External dimensions (mm)
170 150 62
Cut-out (mm)
125 125
Weight
0.780 kg
0.480 kg
Material
Injected thermoplastic (ASA PC). self-extinguishing according to UL94 V0
Operating temperature
-20...+60 ºC
-10...+70 ºC
Storage temperature
-40...+70 ºC
Max. static pressure (flow rate m
3
/h)
50 Pa
Dimensions
Flow curves
Flow
Difference of static pressure (Pa)
124.85
119
15
9 62
08_015_CV002.indd 15
29/1