Page 595 - 0700-schn-encl-10

Basic HTML Version

8/14
20
15
10
5
0
10
20
30
40
∆Pa
m
3
/h
NSYCVF38M230PF
60 Hz NSYCAG92LPF
50 Hz
91,85
80
49
13
9
117
137
92
92
Forced ventilation 38 m
3
/h
General characteristics
● The fans comprise an axial motor, a protective housing on the front and rear
surfaces and a filter designed to retain dust particles.
● This filter can be replaced during operation without risk of contact with the rotating
element.
● The cut-out template supplied with the device avoids the need for marking and
protects the surface of the enclosure during handling.
● RAL 7035 grey in the standard offer with the possibility to change to RAL 7032 by
means of a replacement grille.
Conditions of use
● The outside temperature (Te) must be 5 ºC lower than the desired temperature
(Ts) inside the enclosure.
● The filters that equip the fans must be cleaned and replaced regularly.
● The surrounding environment must be relatively clean and overfrequent filter
replacement should be avoided.
● Bear in mind the pressure losses caused by the outlet element (grille with filter,
ventilation louvre or simple opening) when determining the fan flow rate.
Dimensions
Flow curves
Specifications
Reference
Colour: RAL 7035
NSYCVF38M230PF
NSYCVF38M115PF
NSYCVF38M24DPF
NSYCVF38M48DPF
Free flow rate with standard filter (m
3
/h)
38 (50 Hz) 39 (60 Hz)
38 (50 Hz) 39 (60 Hz)
58
44
Flow rate with 1 outlet grille (m
3
/h)
25 (50 Hz) 26 (60 Hz)
27 (50 Hz) 28 (60 Hz)
39
34
Nominal voltage
230 V (50/60 Hz)
115 V (50/60 Hz)
24 V DC
48 V DC
Voltage range
150 V...250 V
75 V...125 V
10 V...27.6 V
36 V...56 V
Absorbed power (50/60 Hz)
4.5/4.8 W
3.3/3.5 W
3.6 W
3.6 W
Max. intensity (50/60 Hz)
0.16/0.17 A
0.16/0.16 A
0.18 A
70 mA
Noise level
40/41 dB (A)
Bearing
Balls
IP
54
External dimensions (mm)
137 117 49
Cut-out (mm)
92 92
Weight
0.220 kg
0.230 kg
Material
Injected thermoplastic (ASA PC). self-extinguishing according to UL94 V0
Operating temperature
-10...+70 ºC
Storage temperature
-40...+70 ºC
Max. static pressure (flow rate 0 m
3
/h)
29 Pa
Flow
Difference of static pressure (Pa)
08_014_CV001.indd 14
29/1