Background Image
Table of Contents Table of Contents
Previous Page  41 / 132 Next Page
Information
Show Menu
Previous Page 41 / 132 Next Page
Page Background

41

n

Dimensions and weights

1

2

3

straight lengths -

FCF54 (FASCLIC)

technical information

54 mm

50 mm

Ú

300 mm

3 m

FCF54/50

FCF54/100

FCF54/150

FCF54/200

FCF54/300

n

Assembly

n

Loading graphs

mm

L

kg/m mm

L

daN

F

1

mm

L

2

mm

H

kg/1 kg/100 daN.m

mm mm

L

W

FCF54/50

50

2·03

2·03

FCF54/100

100

2·46

2·46

FCF54/150

150

3·46

3·46

FCF54/200

200

4·02

4·02

FCF54/300

300

5·34

5·34

Cat. Nos.

304L

316L

Weight (kg/3 m)

All weights are given in Kilograms (kg) and are for a 3 m straight length

Please use Cat. No. when placing your order, see p. 12

B

o

r

d

S

é

c

u

r

i

t

é

B

r

e

v

e

t

é

Safety

edge

Unclip integral couplers from delivery position, offer secondary length

and press couplers outwards. Bend tabs to secure using screwdriver

No additional fasteners required

Dividers : see p. 46

n

Finishes

Available finishes :

304L

Stainless steel 304L

316L

Stainless steel 316L

For detailed information related to finishes, refer to

p. 116-117

Load tests carried out to IEC 61537 (safety factor 1·7 + joint

1

/

5

th

of the

way along the span). Permissable load should include all cable loads

and any other additional loads (eg: wind, snow)

NOTE:

For more information on loadings, see

p. 125

Sheared steel (particularly stainless steel) does

have relatively sharp edges and protective gloves

must be worn during handling

All dimensions (mm) are nominal

P1500

= supports at 1 500 mm, see

p. 120

for more information

CF 54/50

è

100 CF 54/150

è

200 CF 54/300 CF 54/400 CF 54/500-600

kg/m

mm

304L - 316L

1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500

120

100

80

60

40

20

0

P1500

W

3 000

100

P

a

t

e

n

t

e

d

P

a

t

e

n

t

e

d

P

A

T

E

N

T

E

D

P

A

T

E

N

T

E

D

P

A

T

E

N

T

E

D

PATENTED

Patented

L

F

L

50

10

20

100

H

F

Fast

assembling

L

F

L

50

10

20

100

H

F

Fixing without

nuts and bolts

The permissable load stated in this catalogue represents the load

that Cablofil steel wire cable tray is guaranteed to be able to bear. It

assumes loads are evenly spread and is given in daN/m. The standard

permits a deflection equivalent to 1/100th of the span. Legrand

imposes a stricter limit of 1/200th for both safety and aesthetic reasons.

For example, Legrand voluntarily restricts deflection to 10 mm for a

span of 2 m, whereas the standard would allow 20 mm.