39
n
Dimensions and weights
straight lengths -
CF54
technical information
CF 54/50
è
100 CF 54/150
è
200 CF 54/300 CF 54/400 CF 54/500-600
kg/m
mm
304L - 316L
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
120
100
80
60
40
20
0
P1500
CF54/50
è
100 CF54/150 CF54/200 CF54/00 CF54/400
è
500 CF54/600
1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500
kg/m
mm
EZ - GC - EZ+
P2000
140
120
100
80
60
40
20
0
3 000
54
100
50
W
CF54/50
CF54/100
CF54/150
CF54/200
CF54/300
CF54/400
CF54/450
CF54/500
CF54/600
n
Loading graphs
54 mm
50 mm
Ú
600 mm
3 m
Sheared steel (particularly stainless steel) does
have relatively sharp edges and protective gloves
must be worn during handling
All dimensions (mm) are nominal
B
o
r
d
S
é
c
u
r
i
t
é
B
r
e
v
e
t
é
Safety
edge
mm
L
kg/m mm
L
daN
F
1
mm
L
2
mm
H
kg/1 kg/100 daN.m
mm mm
L
W
CF54/50
50
1·89 1·97 1·97 1·84 1·84
CF54/100
100
2·33 2·42 2·42 2·26 2·26
CF54/150
150
3·13 3·25 3·25 2·69 2·69
CF54/200
200
4·07 4·23 4·23 3·50 3·50
CF54/300
300
6·13 6·37 6·37 5·14 5·14
CF54/400
400
9·15 9·51 9·51 7·92 7·92
CF54/450
450
9·79 10·17 10·17 8·49 8·49
CF54/500
500
10·42 10·83 10·83 9·06 9·06
CF54/600
600
11·69 12·15 12·15 10·20 10·20
Cat. Nos.
EZ
GC
304L
316L
Weight (kg/3 m)
EZ+
All weights are given in Kilograms (kg) and are for a 3 m straight length
Please use Cat. No. when placing your order, see p. 11
P1500
= supports at 1 500 mm, see
p. 120
for more information
NOTE:
For more information on loadings, see
p. 125
n
Finishes
Standard stocked finish :
EZ
Electrogalvanising after manufacture
Additional finishes :
EZ+
Organically coated electrogalvanised after manufacture
GC
Hot dip galvanised after manufacture
304L
Stainless steel 304L
316L
Stainless steel 316L
For detailed information related to finishes, refer to
p. 116-117
Load tests carried out to IEC 61537 (safety factor 1·7 + joint
1
/
5
th
of the
way along the span). Permissable load should include all cable loads
and any other additional loads (eg: wind, snow)
Dividers : see p. 46
➔
Couplers : see p. 48-51
➔
= supports at 2 000 mm, see
p. 120
for more information
P2000
The permissable load stated in this catalogue represents the load
that Cablofil steel wire cable tray is guaranteed to be able to bear. It
assumes loads are evenly spread and is given in daN/m. The standard
permits a deflection equivalent to 1/100th of the span. Legrand
imposes a stricter limit of 1/200th for both safety and aesthetic reasons.
For example, Legrand voluntarily restricts deflection to 10 mm for a
span of 2 m, whereas the standard would allow 20 mm.