![Show Menu](styles/mobile-menu.png)
![Page Background](./../common/page-substrates/page0053.jpg)
51
n
Dimensions
Calculating the panel trunking usable cross section
Graph for H 05 V-K and H 07 V-K cables with 0
·
75 packing coefficient
036200-29131u.eps
8000
7079
8730
9000
7000
6000
5716
5216
5000
4216
4200
3115
3354
3000
2717
2000
300 391
1932
1246
2008
1159
692
720
1000
730
460
100 200 300 400 500 600 700 800 900
10 mm2
6 mm2
4 mm2
2 . 5 mm2
1 . 5 mm2
1 mm2
0 . 75 mm2
Cat. No. 0362 25
Cat. No. 6361 17
Cat. No. 6361 13
Cat. No. 6361 16
Cat. No. 6361 12
Cat. No. 6361 08
Cat. No. 6361 07
Cat. No. 6361 11
Cat. No. 6361 02
Cat. No. 6361 01
Cat. No. 6361 05
Cat. No. 6361 00
8960
Usable
cross section (mm
2
)
Number of conductors
Example :
150 conductors 0
·
75 mm
2
➞
1230 mm
2
cross section and
120 conductors 1
·
5 mm
2
➞
1700 mm
2
cross section
Makes a total of 2930 mm
2
The correct panel trunking is Cat. No. 6361 12, 60 x 60 mm, with a
capacity of 3115 mm
2
‘T’ junctions made easy
Remove
reinforcement
bars at required
length and break
4 . 5
6 . 5
6 . 5
6 . 5
12 . 5
12 . 5
25
25
25
12 . 5
2 000
1 950
8
Width 80 to 120 mm
12 . 5
12 . 5
25
4 . 5
6 . 5
12 . 5
2 000
1 950
8
14
Width 25 to 60 mm
2 000
1 950
8
12 . 5
12 . 5
12 . 5
4 . 5
25
50
Width 15 mm
A
4
B
c036601
Transcab
Cat. Nos.
A (mm)
B (mm) C (mm)
6361 00
25
25
10·1
6361 01
25
40
12·6
6361 06
40
40
12·6
6361 11
60
60
16·1
6361 02
25
60
16·1
6361 07
40
60
16·1
6361 12
60
60
16·1
6361 16
80
60
16·1
6361 20
100
60
16·1
6361 03
25
80
18·6
6361 08
40
80
18·6
6361 13
60
80
18·6
6361 17
80
80
18·6
6361 21
100
80
18·6
6361 25
120
80
18·6
6361 14
60
100
20·6
6361 22
100
100
20·6
6361 23
150
100
20·6
n
Detail of base perforations
1 Clip out the required section width reinforcement bars
and snap out section
2 Form T junction and fix into place
3 Ready for wiring – cut cover to suit
Faster base build without a saw
c036601a
6 . 25
1 . 8
C
12 . 5
6
1
2
3
Trunking width 25 to 120 mm
6 mm gap – 6·5 mm finger width
T
ranscab
®
open slot panel trunking