Table of Contents Table of Contents
Previous Page  158 / 210 Next Page
Information
Show Menu
Previous Page 158 / 210 Next Page
Page Background

158

n

Technical information

Icc 10 kA according to BS EN 60309-1, BS EN 60309-2, IEC 60309-1 and IEC 60309-2

IP rating according to BS EN 60529 and IEC 60529 :

IP 44 when plug inserted

IP 54 when used with IP 66/67-55 straight plugs

IP 55 with cover closed or used with IP 66/67-55 angled plugs

IK according to BS EN 62262 and IEC 62262 :

IK 09 : Plastic

IK 10 : Metal

Stainless steel screws

Brass contacts

Resistance to glow wire and dielectric strength

Glow wire :

960° C for live part supports

650° C for other parts

Dielectric strength : 3 000 V 50 Hz

Temperatures

–20 °C to + 100 °C (+80 °C with auxiliary fitted)

Installation : –20 °C / +40 °C

Use : –20 °C / +100 °C

n

Accessories

Auxiliary contacts (–20 °C to +80 °C)

Prisinter sockets can accommodate two c/o auxiliary contacts (late make/early break) Cat. No. 0521 96 p. 156

These may be used to signal to a central control/monitoring station or control a contactor to remove load

Padlockable cover in closed position

n

Dimensions

Prisinter panel mounting sockets IP 44/55 - LV 16/32/63 A

(p. 156-157)

Hypra Prisinter breaking capacity at 3 x 400 V

±

according to

BS EN 60947-1, BS EN 60947-3, IEC 60947-1 and IEC 60947-3 :

H

20

Drilling

D

D

5 . 5 (16/32 A)

B

A

C

E

=

=

E

G

8 (63 A)

Ø 5 . 3

Ø F

052002-52294c.eps

H

20

Dr lling

D

D

. 5 (16/32 A)

B

A

C

E

=

=

E

G

8 (63 A)

Ø 5 . 3

Ø F

052 02-5 294c.eps

Category

16 A

32 A

63 A

AC 1

16 A

32 A

63 A

AC 23

8·4 kW

16·8 kW

33 kW

AC 3

8·4 kW

16·8 kW

33 kW

Material

Weight

A

B

C

D

E

F (mm)

G

H (mm)

(kg)

(mm)

(mm)

(mm)

(mm)

(mm)

min.

max.

(mm)

max.

LV 16 A

2 P +

T

Plastic

0·42

46

70

132

115

100

92

98

46

6 to 10

Plastic

0·48

46

70

138

115

100

92

96

46

6 to 10

3 P +

T

Metal

1·33

3 P + N +

T

Plastic

0·57

46

75

156

125

110

102

106

51·5

7

Metal

1·47

LV 32 A

2 P +

T

Plastic

0·57

54

77

153

143

125

115

122

58·5

10 to 20

3 P +

T

Plastic

0·61

54

77

153

143

125

115

122

58·5

10 to 20

Metal

1·5

3 P + N +

T

Plastic

0·65

55

79

169

143

125

119

122

58·5

9 to13

Metal

1·8

LV 63 A

3 P +

T

Plastic

0·95

55

99

205

143

125

120

122

59·5

10 to 20

Metal

1·85

3 P + N +

T

Plastic

0·98

55

99

205

143

125

120

122

59·5

10 to 20

Metal

2·2

Hypra

®

Prisinter IP 44/55 - LV 16/32/63 A

p

anel mounting interlocked switched sockets