Cat. Nos.

Voltage (V)

Current (A)

Nominal

cross section

IEC CSA UL Ie IEC CSA UL IEC

(mm

2

)

CSA

(AWG)

UL

(AWG)

0371 00/20/30/60

800 600 600

27 24 20 20 2 . 5 12 12

0371 01/21/31/61

36 32 30 30 4

10 10

0371 02/62

48 41 50 50 6

8

8

0371 03/63

63 57 60 60 10

6

6

0371 04/64

85 76 85 85 16

4

4

0371 05/65

138 125 115 115 35

2

2

0371 07/67

500 300 300

27 24 20 20 2 . 5 12 12

0371 08/68

36 32 30 30 4

10 10

0371 09/69

36 32 30 30 4

10 10

0371 66

1000 600 600 213 192 200 200 70 000 000

0371 77

800 600 600 36 32 30 30 4

10 10

0371 78

48 41 50 50 6

8

8

n

Characteristics and dimensions (mm)

V2 polyamide according to UL 94, 960 °C according to IEC EN 60695-2-11

Connection blocks

Protection blocks

Disconnection blocks

Power according to EN 60947-7-3

Approved by ATEX :

LCIE 07 ATEX 0010 U-0081 II 1 or 2 G or D Ex e/i/tD/iD II

The terminal blocks with screw connection covered by this certificate

are 1-, 2- and 3-level connection terminal blocks, and protection blocks

with metal

1

and plastic base (detailed list on p. 118)

The main characteristics are :

Operating temperature : –30 °C to +55 °C

Maximum temperature of materials : +85 °C

Working voltage acc. to EN 60079-7 : 1-level terminal blocks : 500 V

Blocks with 2 entries - 2 exits : 250 V

2 and 3-level terminal blocks : 250 V

Rated current:

Cat. No. 0371 51 : see blocks for sensors

IEC 60947-7-1, CSA no. 22-2 no. 158, UL 1059

Ie: Rated current NF C 15100 table 52H, column 4

IEC 60947-7-1/7-2, CSA no. 22-2 no. 158, UL 1059

1 : PEN terminal blocks

IEC 60947-7-1/7-3, CSA no. 22-2 no. 158, UL 1059

Cat. Nos. 0371 00/01/

02/03/20/21/30/31/60/

61/62/63/77/78

Cat. Nos.

0371 04/05/64/65

Cat. Nos.

0371 70/71/72/73

Cat. No. 0371 80

Cat. No. 0371 87

Cat. Nos. 0371 77/78

Cat. Nos. 0371 09/69

Cat. No. 0371 66

Cat. Nos. 0371 74/75

Cat. Nos. 0371 81/82/83/85

Cat. No. 0371 79

Cat. No. 0371 76

Cat. Nos. 0371 84/86

Cat. Nos. 0371 07/08/67/68

52·2

45·8

46·4

53·9

57·1

54·5

62·9

70·4

52·2

45·8

46·4

53·9

71·2

26·8

46·4

53·9

52·2

45·8

46·4

53·9

57

54·4

51·2

58·7

64·6

62

63

70·5

54·5

63

70·5

91·6

71·2

26·8

52·3

83·1

90·6

59·8

57

54·4

51·2

58·7

50·5

29·3

41·5

49

36·8

84·2

71·2

26·8

46·5

76·3

83·8

54

74·8

72·2

62·5

70

Conductor

cross section (mm

2

)

2 . 5

4

6

10

16

35

70

Rated current (A)

18

23

30

42

57

93

144

Certificate of conformity of components is available on request

1 : Except for Cat. No. 0371 76

Cat. Nos.

Voltage (V)

Nominal cross section

IEC CSA UL IEC (mm

2

) CSA (AWG) UL (AWG)

0371 70

800 600 600

2 . 5

12

12

0371 71

4

10

10

0371 72

6

8

8

0371 73

1

10

6

6

0371 74

1

16

4

4

0371 75

1

35

2

2

0371 76

35

0371 77

800 600 600

4

10

10

0371 78

6

8

8

0371 79

500 300 300

4

10

10

Cat. Nos.

Voltage (V)

Current (A)

Nominal

cross section

IEC CSA UL IEC CSA UL IEC

(mm

2

)

CSA

(AWG)

UL

(AWG)

0371 80

500 300 300 15 15 15

2 . 5 12 12

0371 81 or

0371 80 + 0375 15

250 250 250 6 . 3 6 . 3 6 . 3

0371 82

500 300 300 15 15 15

0371 83

0371 84

0371 85

0371 86

0371 87

250 250 250 10 10 10 10

Cat. Nos.

Short-circuit

Short-circuit + overload

Separate blocks Assembled blocks Separate blocks Assembled blocks

0371 81 or

0371 80

4 W / 6 . 3 A

1 . 6 W/6 . 3 A 1 . 6 W/6 . 3 A

Pvk = 4 . 75 W Pvk = 2 W Pv = 1 . 65 W

0371 87

4 W

2 . 5 W

1 . 6 W

Pvk = 5 W Pvk = 2 . 7 W Pv = 1 . 8 W

65·5

65·5

73

128