Background Image
Table of Contents Table of Contents
Previous Page  68 / 132 Next Page
Information
Show Menu
Previous Page 68 / 132 Next Page
Page Background

68

SCP

super compact busbar

expansion and transposition lengths

Pack

Cat. Nos.

Expansion lengths

Standard – 3 m

Absorb the thermal expansion

during normal use that, on long

runs, would otherwise cumulate

and put abnormal force on the

connection points

Expansion length is to be placed

in straight runs of more than 40 m

and repeated every 40 m

Single bar

Aluminium

Copper

Rating (A)

1

602

8

0290P

630

1

602

8

0291P 652

8

0290P 800

1

602

8

0292P 652

8

0291P 1 000

1

602

8

0294P 652

8

0293P 1 250

1

602

8

0296P 652

8

0295P 1 600

1

602

8

0297P 652

8

0296P 2 000

1

652

8

0298P 2 500

Double bar

Rating (A)

1

603

9

0294P

2 500

1

603

9

0296P 653

9

0295P 3 200

1

603

9

0297P 653

9

0296P 4 000

1

653

9

0298P 5 000

Pack

Cat. Nos.

Transposition lengths

Phase transposition – 1·2 m

In runs exceeding 100 m it is

recommended to include two

transposition lengths to balance

mutual phase reactance and

electric impedance (one at 1/3

and one at 2/3 distance of the run)

Single bar

Aluminium

Copper

Rating (A)

1

602

8

7100P

630

1

602

8

7101P 652

8

7100P 800

1

602

8

7102P 652

8

7101P 1 000

1

602

8

7104P 652

8

7103P 1 250

1

602

8

7106P 652

8

7105P 1 600

1

602

8

7107P 652

8

7106P 2 000

1

652

8

7108P 2 500

Double bar

Rating (A)

1

603

9

7104P

2 500

1

603

9

7106P 653

9

7105P 3 200

1

603

9

7107P 653

9

7106P 4 000

1

653

9

7108P 5 000

Neutral rotation – 1·0 m

When the sequence of the

distribution board phases is

different to that of the transformer

Single bar

Rating (A)

1

602

8

7140P

630

1

602

8

7141P 652

8

7140P 800

1

602

8

7142P 652

8

7141P 1 000

1

602

8

7144P 652

8

7143P 1 250

1

602

8

7146P 652

8

7145P 1 600

1

602

8

7147P 652

8

7146P 2 000

1

652

8

7148P 2 500

Double bar

Rating (A)

1

603

9

7144P

2 500

1

603

9

7146P 653

9

7145P 3 200

1

603

9

7147P 653

9

7146P 4 000

1

653

9

7148P 5 000

1 2 3 N

N 1 2 3

N 1 2 3

N 3 1 2

1 2 3 N

N 1 2 3

N 1 2 3

N 3 1 2

Single bar expansion length

Single bar phase

transposition length

3

N 1 2 3

N 3 1 2

Single bar neutral

rotation length

High power busbar from 630 A to 4 000 A with aluminium alloy conductors and from 800 A to 5000 A with copper conductors

SCP complies with BS EN 60439-2

Designed to be maintenance-free, except for the periodic and compulsory inspections required by the Standard IEC 60364

Supplied with electrical junction monobloc system pre-installed

Selection charts p. 62-65 Dimensions and technical information p. 95 Technical data p. 112-117

Key : How to select the correct configuration of bar

The 4

th

digit of an SCP Cat. No. determines the busbar configuration

All examples on this page show 4 conductor versions, ie.

8

or

9

;

5 conductor and 200% neutral versions are available by substituting

the 4

th

digit with

4

,

5

,

6

or

7

, as shown below

3L + N + PE 3L + N + FE+ PE 3L + 2N + PE

Single bar

8

4

5

Double bar

9

6

7