sollysta Wiring Accessories Guide

11

“ A device used for isolation needs to

prevent inadvertent reclosure ”.

Fused connection units

A 13A fused connection unit could be used for many

applications. One of which could be to supply an electric

towel rail in a bathroom. This equipment may need to be

isolated for inspection, testing or maintenance.

Such a unit if used for isolation needs to be designed or

installed so as to prevent unintentional or inadvertent closure

as described in 537.2.2.3. Therefore if the fused connection

is not under the immediate supervision of the person

working on the towel rail then the whole circuit may have to

be isolated at the distribution board.

Alternatively the fused connection unit may have a

feature whereby it can be locked with the fuse carrier out and

thereby satisfying the regulations as far as securing the

isolation is concerned. BS 7671 table 53.2 identifies

BS 1363-4 as a device suitable for isolation