Data is subject to errors and technical modifications.
1.45
MCCBs x250
MCCBs x250 25kA
Characteristics
-
-
Thermal magnetic trip unit, two versions: Z version: fixed thermal and fixed magnetic. H version: adjustable thermal
magnetic.
-
-
Access to mechanical test button on cover.
-
-
Lockable cover protects MCCB settings.
-
-
Integrated padlocking handle: Ø 4mm.
-
-
Connection capacity: 150mm² rigid cables, palm lug max. width: 25mm
-
-
Conforms to BS EN 60947-2
-
-
AC 22/23A.
-
-
For technical data see page
1.106.x250 25kA
-
-
Fixed thermal: 1x I n
-
-
Fixed magnetic: > 10 x I n
x250 40kA
-
-
Adjustable thermal: 0.63, 0.8, 1 x I n
-
-
Adjustable magnetic: 6 - 8 - 10 - 13 x I n (100 - 200A). 5 - 7 - 9 - 11 x I n (250A).
Description
Breaking capacity
Cat ref. 3P
Moulded Case Circuit Breakers 25kA - Fixed
MCCBs x250 - 100A
I cs : 20 kA, I cu: 25 kA
HHB100Z
MCCBs x250 - 125A
I cs : 20 kA, I cu: 25 kA
HHB125Z
MCCBs x250 - 160A
I cs : 20 kA, I cu: 25 kA
HHB160Z
MCCBs x250 - 200A
I cs : 20 kA, I cu: 25 kA
HHB200Z
MCCBs x250 - 250A
I cs : 20 kA, I cu: 25 kA
HHB250Z
Moulded Case Circuit Breakers 40kA - Fixed
MCCBs x250 - 100A
I cs : 20 kA, I cu: 40 kA
HNB100Z
MCCBs x250 - 125A
I cs : 20 kA, I cu: 40 kA
HNB125Z
MCCBs x250 - 160A
I cs : 20 kA, I cu: 40 kA
HNB160Z
MCCBs x250 - 200A
I cs : 20 kA, I cu: 40 kA
HNB200Z
MCCBs x250 - 250A
I cs : 20 kA, I cu: 40 kA
HNB250Z
Moulded Case Circuit Breakers 40kA - Adjustable
MCCBs x250 - 100A
I cs : 20 kA, I cu: 40 kA
HNB100H
MCCBs x250 - 125A
I cs : 20 kA, I cu: 40 kA
HNB125H
MCCBs x250 - 160A
I cs : 20 kA, I cu: 40 kA
HNB160H
MCCBs x250 - 200A
I cs : 20 kA, I cu: 40 kA
HNB200H
MCCBs x250 - 250A
I cs : 20 kA, I cu: 40 kA
HNB250H
Moulded Case Circuit Breakers x250 25kA
HDA125Z
Commercial