5.45

Data is subject to errors and technical modifications.

Wiring

Accessories

IP66

Ingress Protection (IP) Chart

The IP rating for all low voltage enclosures up to 1000 V a.c. and 1500 V

d.c. is defined in identical fashion by the standards EN 60529 - IEC 529. It

comprises the letters IP followed by two character numerals and or additional/

supplementary letters.

The first character numeral indicates the degree of protection

provided by the enclosure against access to hazardous parts by preventing or

limiting the ingress of a part of the human body or an object held by a person

and ingress of solid foreign objects.

The first character numeral:

Protection against foreign objects

IP

Description

0

Non-protected

1

Protected against solid objects ≥ than 50mm

2

Protected against solid objects ≥ than 12.5mm

3

Protected against solid objects ≥ than 2.5mm

4

Protected against solid objects ≥ than 1.0mm

5

Dust-protected

6

Dust-tight

The second character numeral indicates the degree of protection provided

by the enclosure with respect to harmful effects on the equipment due to the

ingress of water. An X signifies that the tests are not applicable to the product.

The second character numeral:

Protection against ingress of water with harmful effects

IP

Description

0

Non-protected

1

Protected against vertically falling water drops

2

Protected against vertically falling water drops

when enclosure titled up to 15°

3

Protected against spraying water

4

Protected against splashing water

5

Protected against water jets

6

Protected against powerful water jets

7

Protected against the effect of temporary

immersion in water

8

Protected against continuous immersion in

water

Additional letter (in option)

Protection of people against access to hazardous parts

Description

A

Protected against access to hazardous parts with the

back of the hand

B

Protected against access to hazardous parts with a finger

C

Protected against access to hazardous parts with a tool

- ø 2.5mm

D

Protected against access to hazardous parts with a wire

- ø 1mm

Additional letter (in option)

Specific information on the product

Description

H

High voltage apparatus

M

Motion during water test

S

Stationary during water test

W

Weather conditions