4.18

Data is subject to errors and technical modifications.

Residential

Distribution

Miniature Circuit Breakers

Technical Information

Connection

The circuit breaker can have the line\load connected to either the top or bottom terminals

Temperature Derating

MCBs are designed and calibrated to carry their rated current and to operate within their designated thermal time/current zone at 30ºC. Testing is carried out with

the breaker mounted singly in a vertical plane in a controlled environment. Therefore if the circuit breaker is required to operate in conditions which differ from the

reference conditions, certain factors have to be applied to the standard data.

I

n

(A)

-25ºC -20ºC -15ºC -10ºC -5ºC 0ºC 5ºC 10ºC 15ºC 20ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC

6

8.64 8.4 8.16 7.92 7.68 7.44 7.2 6.96 6.72 6.48 6.24 6

5.76 5.52 5.28 5.04 4.8 4.56

10 14.4 14 13.6 13.2 12.8 12.4 12 11.6 11.2 10.8 10.4 10 9.6 9.2 8.8 8.4 8

7.6

16 23 22.4 21.8 21.1 20.5 19.8 19.2 18.6 17.9 17.3 16.6 16 15.4 14.7 14.1 13.4 12.8 12.2

20 28.8 28 27.2 26.4 25.6 24.8 24 23.2 22.4 21.6 20.8 20 19.2 18.4 17.6 16.8 16 15.2

25 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19

32 46.1 44.8 43.5 42.2 41 39.7 38.4 37.1 35.8 34.6 33.3 32 30.7 29.4 28.2 26.9 25.6 24.3

40 57.6 56 54.4 52.8 51.2 49.6 48 46.4 44.8 43.2 41.6 40 38.4 36.8 35.2 33.6 32 30.4

50 -

-

-

-

-

62 60 58 56 54 52 50 48 46 44 42 40 38

63 -

-

-

-

-

-

-

-

-

-

-

63 60.5 58 55.4 52.9 50.4 47.9